16
ETS
‐
text
Dynamic range
[default value]
Comment
Alarm Duration Difference
Sending
Telegram is sent when there is a duration difference
between current counting and the previous value sent.
This duration difference can be a range of 0 - 2800000
sec, the device is recording but will not send out any
telegram when the difference is set at “0”.
Alarm Counter Difference
Sending
Alarm Counter
Cyclic Sending
[0]
[0]
0-2,800,000
0-500
OFF, 1min, 2min, 3min, 4min, 5min,
10min, 15min, 20min, 25min, 30min,
1hour, 2hours, 3hours, 4hours, 5hours,
6hours, 7hours, 8hours
[OFF]
Telegram is sent when there is a count difference
between current counting and the previous value
sent. This count difference can be a range of 0 - 500,
the device is recording but will not send out any telegram
when the difference is set at “0”.
Send telegram at intervals you desired
Number
Name
Length
Usage
25, 28, 31,
34
26, 29, 32,
35
27, 30, 33,
36
Alarm 1, 2, 3, 4
Count 1, 2, 3, 4
Duration 1, 2, 3, 4
1bit
2bytes
4bytes
When the measured value is above/below the threshold
a telegram with value 0 or 1 is sent. When the
measurement values return to the normal range(less/
higher than the hysteresis) a telegram with value 0 or 1
is sent.
The device sends the number counted value of threshold
events for output current, output voltage or device
temperature.
The device sends the total duration time (in second) for
output current, output voltage or device temperature.
The following chart shows the objects that belong to general setting: