Connector Pin No. Assignment (CN47)
※
Connector Pin No. Assignment (CN55)
3.
Functions
3.1
Input Voltage Range
3.2
Inrush Current Limiting
3.3
Output Power
◎
.
The input voltage range is
or
AC90~264V
DC127~370V
◎
To insure proper operation, AC input should be within the pre-specified range. A wrong input will cause the supply unit operating
improperly, losing PFC function or even damaging the unit in a worst case scenario.
with a lower input voltage. Please refer to 4.2 Derating for more information.
inrush current of the unit.
specified value if the input thermistor is not allowed sufficient time to cool down. After turning off the supply, a 10 second cool down
period is recommended before turning them on again.
◎
The efficiency will be lower and the output current will be automatically limited to a predetermined safe value if the unit
is applied
◎
.
Built-in inrush current limiting circuit
PHP-3500-24 : 3480W (24V / 145A)
PHP-3500-48 : 3504W (48V / 73A)
◎
If adding an external switch (a relay/ a circuit breaker) at the input side is required, choose switches that are able to withstand
◎
Since the inrush current limiting circuit mainly consists of a NTC thermistor and a relay, inrush current will be much higher than the
3.4
Power Factor Correction (PFC)
◎
Built-in active power factor correction (PFC) function, power factor (PF) will be 0.95 or better when input voltage is in a range of
90-230Vac and operated at full load condition. PF will be less than 0.95 if the output is not at full load or the input voltage is higher
than 230Vac.
Pin No.
Function
Description
21,22
For PMBus model: Serial Data used in the PMBus interface. (Note.2)
For CANBus model: Data line used in CANBus interface. (Note.2)
SDA
CANH
17,18
The signal return is isolated from the output terminals (+V & -V).
GND-AUX(S)
Connection for constant current level programming. (Note.1)
3,4
PC
2
+V (Signal)
Positive output voltage signal.
1
-V (Signal)
Negative output voltage signal.
Connection for output voltage programming. (Note.1)
5,6
PV
7,8,9,10,11,12
NC
13,14,15,16
Differential digital signal for parallel control. (Note.1)
DB,DA
19,20
For PMBus model: Serial Clock used in the PMBus interface. (Note.2)
For CANBus model: Data line used in CANBus interface. (Note.2)
SCL
CANL
Note1: Non-isolated signal, referenced to [-V(signal)].
Note2: Isolated signal, referenced to GND-AUX(S).
Note1: Non-isolated signal, referenced to [-V(signal)].
Note2: Isolated signal, referenced to GND-AUX(S).
Pin No.
Function
Description
3
The unit can turn the output ON/OFF by electrical signal or dry contact between
and
. (Note.2)
Remote ON/OFF
+12V-AUX
Short (10.8 ~ 13.2V) : Power ON ; Open (-0.5 ~ 0.5V) : Power OFF ; The maximum input voltage is 13.2V.
Remote
ON-OFF
5
Low (-0.5 ~ 0.5V) : When Vout
80%
5%.
≧
±
The maximum sourcing current is 4mA and only for output. (Note.2)
DC-OK
1
Auxiliary voltage output, 10.8~13.2V, referenced to
.
GND-AUX (pin 2)
The maximum load current is 0.5A. This output has the built-in "Oring diodes" and is not controlled by the
control.
Remote ON/OFF
+12V-AUX
Auxiliary voltage output GND. The signal return is isolated from the output terminals (+V & -V).
2
GND-AUX
4
GND-AUX(S)
6
High (3.5 ~ 5.5V) : When the internal temperature exceeds the limit of temperature alarm.
Low (-0.5 ~ 0.5V) : When the internal temperature is normal, and when fan works normally.
T-ALARM
High (3.5 ~ 5.5V) : When the Vout
80% 5%.
≦
±
The maximum sourcing current is 4mA and only for output(Note.2)
The signal return is isolated from the output terminals (+V & -V).
-----
2
1
22
21
2
1
6
5