MPCIB 396 P6
mect s.r.l.
ME3025_13 03/21
15
n seq.
Key to
press
Appears
on the
display
NOTES
appears on the display (see “COEN function”
paragraph)
**(press “prog.
” to confirm)
28
CoEnC
29
dIUSon
DIVISION FACTOR TOTAL COUNTING
30
prog.
10000
Set division factor value (1
65535). This number
will be the denominator of the correction constant
**(press “prog.
” to confirm)
31
dIUSon
32
Reset
Exit
“measure”
** see para. “SET-UP” to change the set value.
2.2 "nUnEr" and “dEnon” FUNCTION (multiplying factor)
It is possible to programme a correction factor, which multiplies or divides the
number pulses received at the input, visualizing them as you desire. The two menu
items that you have to programme mean:
nUnEr
display readout = ______________ * CoEnC * Input pulses
dEnon
For a reading without correction factor is sufficient to set up nUnEr = dEnon, instead
to add corrective constant is necessary to set up “nUnEr” and “dEnon” to get the
desired value.
As described in “CoEnC function” paragraph, it is possible to obtain multiplying
factors using the reading of the encoder’s edges (see paragraph).
Now is shown an applicative example; for the set up instruction see Table 3.
119 pulses/revolution encoder and it is requested a visualisation of 100
digits/revolution
display readout
K = _________________
input pulses
Programme “100” at the “nUnEr” item and 119 at the “dEnon” item ( CoEnC = F1).