MPCIB 396 P6
mect s.r.l.
ME3025_13 03/21
24
n°
seq.
Touch
key
Appears
on the
display
REMARKS
ECC-dIS = acti deactivation delay
nO dLY = no delay
Select the desired item by "
" key and confirm with
“prog.
”
23
SEL.d
24
dELAY
AL1 TIME SET-UP
25
prog.
00 25.0
Set up a number between 0 and 25.0 sec.
** (press “prog.
” to confirm)
26
dELAY
27
AL01
25
AL02
ALARM 2 PARAMETERS
26
prog.
tIPOAL
KIND OF ALARMS SELECTION
27
prog.
FInES
FinES = windowed alarm
SOGLIA = threshold alarm
dELtA = delta rispetto allarme1
Select the desired item by "
" key and confirm with
“prog.
”
28
tIPOAL
29
rELE
ALARM 2 FUNCTIONING CONFIGURATION
30
prog.
NA
n.A. = relay normally open
n.C. = relay normally closed
Select the desired item by "
" key and confirm with
“prog.
”
31
rELE
32
SP 1
First trigger set point SET UP
33
prog.
0 00000
Set up the SP1 value. **(Confirm by “prog.
”)
34
SP 1
35
SP 2
Second trigger set point SET UP. Program only if the
functioning of the windowed alarm is requested.
36
prog.
0 00000
Set up the SP2 value. **(Confirm by “prog.
”)
37
SP 2
38
HY
ALARM 2 HYSTERESIS SET-UP
39
prog.
00 250
Set up a number between 0 and 250 digit.
** (press “prog.
” to confirm)
40
HY
41
SEL.d
AL2 TIME CONFIGURATION
42
prog.
ECC
ECC = activation delay
dIS = deactivation delay