MPCIB 396 P6
mect s.r.l.
ME3025_13 03/21
29
** to modify the number set-up see the procedure illustrated in the paragraph “SET-
UPS”.
4.3 NOTES ON THE SET UP OF ANALOGUE OUTPUTS
Program instrument with the following calibration:
READING: 100
AMMETER OUTPUT: 5 mA ;
READING: 10000
AMMETER OUTPUT: +15 mA;
The instrument parameters should be programmed as follows.
PARAMETERS "OUt AN":
SEL. OA
= C0.20
IS
= 100
FS
= 10000
ISO
= 5.00 *
FSO
= 15.00 *
* with display below “100” the analogue output is fixed to 5 mA; with display above
“10000” the analogue output is fixed to 15 mA.
Program instrument with the following calibration:
READING: 100
AMMETER OUTPUT: 4 mA ;
READING: 10000
AMMETER OUTPUT: 20 mA ;
The instrument parameters should be programmed as follows.
PARAMETERS “OUt AN.”
SEL.OA
= C 4.20
IS
= 100
FS
= 10000
ISO
= not necessary to program
FSO
= not necessary to program
* with display below “100” the analogue output is fixed to 4 mA; with display above
“10000” the analogue output is fixed to 20mA.
Program instrument with the following calibration:
READING: 100
VOLTMETER OUTPUT: 2 V
READING: 1000
VOLTMETER OUTPUT: 6 V
The instrument parameters should be programmed as follows.
PARAMETERS "OUt AN.":
SEL.OA = E0.10
IS = 100
FS = 10000
ISO = 2.00 *
FSO = 6.00 *
with display below “100” the analogue output is fixed to 2V; with display above
“10000” the analogue output is fixed to 6V.