MPCIB 396 P6
mect s.r.l.
ME3025_13 03/21
36
PR
PrESEt
Read/write
ASCII 0 ÷
+ -999999
PT
P.dEC
(decimal point)
Read/write
Hexadecimal
0 = no point
1 = 99999.9
2 = 9999.99
3 = 999.999
4 = 99.9999
5 = 9.99999
NU
NUnEr
(multiplying factor)
Read/write
ASCII 1 ÷ 65535
DN
dEnon
(division factor)
Read/write
ASCII 1 ÷ 65535
RS
Display reset
Only write
Hexadecimal
1 = zeroing
RT
Totalizator reset
Only write
Hexadecimal
1 = zeroing
LT
Total counting
Read/write
ASCII
RO
Read out (display)
Only read
ASCII + -999999
AR
Generic status word
Read/write
Hexadecimal
(see paragraph)
A1-A2-A3
SP1 (AL1-AL2-AL3) Read/write
ASCII + -999999
B1-B2-B3
SP2 (AL1-AL2-AL3) Read/write
ASCII + -999999
H1-H2-H3
HY (AL1-AL2-AL3) Read/write
ASCII 0 ÷ 250
D1-D2-D3
Delay (AL1-AL2-
AL3)
Read/write
ASCII 0 ÷ 25.0
W1-W2-W3
Alarm status word
Read/write
Hexadecimal
(see paragraph)
* The code is composed by the letter followed by the number of the alarm to program
5.5 TRANSMISSION OF HEXADECIMAL VALUES
Some values must be transmitted in a 4 digit hexadecimal format. In that case the
protocol string must be preceded by the ASCII character “>“.
EXAMPLE: the string for reading or writing the decimal point in the position 1999.9
will be:
Blank Blank Blank > 0001
EXAMPLE TO READ DECIMAL POINT POSITION
HOST:
EOT 0 0 1 1 P T ENQ
04 30 30 31 31 50 54 05
INSTRUMENT MPCIB396 P6
STX P T blank blank blank > 0 0 0 4 ETX BCC