Basic Connections

 

EM Stop  Buttons, 

Thermal links  

(Normally closed) 

 

For multiple, connect in 

series.  

230v Supply 

3Amp Fused Spur 

Gas Solenoid 

Earth Connections not shown 

Mains Rated  

Potential free contact,  

Max  load 5amp’s 

(latching relay) 

For BMS or sounder/beacon 

activation 

    Wiring information 

All current wiring regulations must be followed with reference to running low and mains voltage cables together. 
 
The maximum cable length between a detector and the control panel should not exceed 100 metres, if the distance between 
the main panel and the detectors is greater than 20metres a 1mm screened cable must be used on the +VE, 0v terminals 

 

Gas detectors, require a four core screened Belden type security cable or 600v rated BMS cable (max cable length of 
100meters.)  
Remote emergency stops and thermal links require a two core screened cable. 
Warranty will be void if Fire Protection Cable or cable over 1mm dia. is used on the SELV side. 

AGDS-2em v2 

Medem Gas detectors 

4 Core wiring

 

Multiple, connect in 

parallel  

Summary of Contents for AGDS-2em v2

Page 1: ...and commissioned to the satisfaction of the manufacturer A commissioning certificate must be issued to the end user along with instructions for the operation of the equipment As the Manufacturer Medem UK should commission this safety system whereupon a commissioning report will be forwarded to the installing agent who should provide a copy to the end user At the point of our commissioning an indiv...

Page 2: ...set to address 1 or 2 Once connected and addressed you are required to learn the sensors to the panel by pressing the LEARN DETS 10 button Each sensor unit has an LED which shows green when power is applied Note There is a warm up period after initial power up of approximately 90 seconds During this time the green LED will flash once per second and the output signal will be inhibited This is to pr...

Page 3: ... N C circuit 8 Remote emergency stop buttons SELV multiple buttons connect in series requires a N C circuit 9 Detector high alarm Time To Isolate adjustment 1 64 10 Learn detectors 11 Disable audible alarm sounder 12 BMS Relay Can be set to report one of the status s in the table below Max switching 230 volts 5amp s AGDS 2em v2 Power at 230 volts from a 2 1 3 4 6 5 12 9 8 7 11 10 1 2 3 4 EM Stop E...

Page 4: ... cables together The maximum cable length between a detector and the control panel should not exceed 100 metres if the distance between the main panel and the detectors is greater than 20metres a 1mm screened cable must be used on the VE 0v terminals Gas detectors require a four core screened Belden type security cable or 600v rated BMS cable max cable length of 100meters Remote emergency stops an...

Page 5: ...ed in series with the EM stop buttons To EM Stop connections in the panel Indicator bar shows when pressed Normal EM Stop Activated Multiple Stop Buttons Single Stop Buttons Resetting indicator bar The stop buttons supplied by Medem are of a Push Glass key resettable style when activated a yellow indicator bar will show and the unit will require resetting using the key provided Multiple stop butto...

Page 6: ...s own instructions for more guidance All current wiring regulations must be followed with reference to running low and mains voltage cables together The maximum cable length between a detector and the control panel should not exceed 100 metres if the distance between the main panel and the detectors is greater than 20metres a 1mm screened cable must be used on the VE 0v terminals Gas detectors req...

Page 7: ...m from the potential source Care should be taken so they are not located close to the edge of a canopy or in direct flow of the supply or extract ventilation For additional information or guidance on site specific requirements please don t hesitate to contact us Each detector has its own Bi Colour LED which is used to indicate the status of that detector Not Lit No power comm s These a four wire u...

Page 8: ...UK will exchange faulty valves for return to the manufacturer 5 Where a Medem UK engineer or another company appointed by Medem UK commission and installed system then that system will carry a ten year warranty This applies to the main panel and the sender unit At the time of commissioning a security label with a serial number will be attached to the main panel box photographs and a comprehensive ...

Page 9: ... links in series to the terminals marked EM STOP 8 3 Each detector has a rotary address switch each switch should be set to a different number 1 2 Then connect the gas detectors to terminals marked DETETORS 6 on the panel Detectors are wired in parallel Daisy chain 4 Connect the fire alarm input to the terminals marked FAP Ensure volt free n c 7 5 Ensure any BMS connections are made to the BMS1 Re...