17
Troubleshooting
Power LED Cleaning
Alert LED
On
Off
In normal operation.
The cleaning alert LED will remain off.
Off Off
Likely cause
No power to bar
Action
Check 24V Power Supply over pins 1
and 3. (Brown and Blue wires)
On
Flashing
Red
Likely cause
Contamination causing a drop in
performance.
Action
Switch off power supply and clean as
described in Maintenance section.
Turn power on and Check for Green
flashing LED
On
Constant
Red
Likely Cause
Abnormal output current detected
Action
Check installation for metallic objects
on the emitter pins
Should the solid red LED persist,
contact your Meech distributor.
Repairs And Warranty
The Meech 971IPS Bar is warranted by Meech Static Eliminators Ltd. to the original
purchaser against defects in material and workmanship for one year after purchase.
Should any malfunction occur, please return the bar directly to Meech Static
Eliminators Ltd. or your local Meech Distributor. All products returned to the factory
MUST be accompanied by a return authorisation number and must be shipped
prepaid. For prompt service, ship the unit to the factory with the return authorisation
number shown clearly on the label. Be sure that it is well packed in a sturdy carton
with shock absorbing material.
Include a note stating the nature of the problem as specifically as possible, and also
include instructions for returning the bar to you. We will pay one-way return shipping
costs on any repairs covered under the warranty.