background image

 

Installation guide solar modules 

 

 

V1 – April 2015 

11 - 19 

 

4.7

 

Install the module in an area free of shade: 

Even a low degree of shading will have a negative effect on the system yield. Therefore, the system must be 

installed in a location without shading. The module should never be shaded completely during the whole 

year

 

4.8

 

Maximizing Power Output through Bifaciality 

Output power in increased proportionally to albedo received by rear side of modules 

The available albedo light that hits the back of the module is directly related to the height (and tilt angle) of 

the module installed over the surface. 

 

o

 

Choose  the  highest  possible  Surface  Reflectivity/Albedo

,  such  as  a  white  roof  or  white  ground 

surface covering. 

o

 

Avoid shading the back side of the module by the support rack.  

o

 

Elevate  the  modules  above  the  mounting  surface  as  much  as  possible.    For  flat  ground/rooftop 

installation it’s recommended a minimum height of 50-70 cm 

o

 

With  tilted  rooftop  installation,  ensure  an  appropriate  ventilation  on  back  to  reduce  an 

accumulation of heat with adverse effects on the performance. 

 

4.9

 

Ensure that the modules are grounded properly: 

Under  the  terms  of  MegaCell,  grounding  of  the  module  frame  (if  present)  is  not  required  for  fault-free 

operation.  To  reduce  the  risk  of  electric  shock  (e.g.  due  to  static  charge)  as  far  as  possible,  MegaCell 

recommends  to  ask  an  experienced  installer  to  carry  out  a  proper  grounding.  If  an  external  lightning 

protection  system  has  been  already  installed,  the  PV  system  has  to  be  integrated  in  the  existing  lightning 

protection concept by a specialist.  

Country-specific  standards  and  regulations  must  be  observed.  The  grounding  connections  between  the 

modules  must  be  checked  and  accepted  by  a  qualified  electrician.  Furthermore,  the  main  grounding  may 

only  be  connected  by  a  qualified  electrician.  In  the  USA  and  Canada,  a  grounding  method  approved  by 

Underwriters Laboratories (UL) is obligatory. To provide proper grounding, an optimal electrical conductivity 

is required. For this purpose, grounding holes are provided at the rear of the module frame (if present).These 

grounding holes are marked by a stamped ground symbol. 

 
 

For  grounding  we  recommend  the  Solklip  grounding  terminal  with  integrated 

thread cutting screw, (UL 467 approved, UL number E69905), manufactured 

by Tyco Electronics. 

Observe  the  additional  instructions  at  www.tycoelectronics.com.  These 

grounding  terminals  accommodate  4  mm²  (AWG  12)  and  6  mm²  (AWG  10) 

stripped solid copper wires. The wires must not be cut, notched or scratched. 

No further preparation is required. 

 

 

Summary of Contents for MBA-GG60 BiSoN Series

Page 1: ...Document name MCELL_PV_Modules_Installation_Manual_EN_v1 2_20150715 Revision date V1 2 July 2015 www megacell it SAFETY AND INSTALLATION MANUAL BIFACIAL SOLAR MODULES...

Page 2: ......

Page 3: ...allowable maximum mechanical loading 10 4 4 Make sure that the surroundings are suitable 10 4 5 The correct location for installation 10 4 6 Yield maintenance through optimal alignment and inclination...

Page 4: ...Installation guide solar modules V1 April 2015 4 19...

Page 5: ...Installation guide solar modules V1 April 2015 5 19 1 MODULES 1 1 MBF GG60 BiSoN series with frame 1 2 MBA GG60 BiSoN series frameless...

Page 6: ...oduct are beyond company control MegaCell does not assume responsibility and expressly disclaims liability for loss damage or expense resulting from improper installation handling or use The informati...

Page 7: ...d after installation to calculate correctly inverter cables and connection size Serial number Each individual module is identified by a unique serial number accompanied with a barcode They are permane...

Page 8: ...r modules generate electricity When exposed to light a voltage occurs which can be dangerous and life threatening Even though the individual modules generate a relatively low voltage of 50 V DC the vo...

Page 9: ...and safe unpacking Please refers to the instructions printed on the cartoon box of each pallet The modules are sensitive technical components which must be handled with utmost care Therefore be partic...

Page 10: ...re that after installation the module is neither subjected to artificially concentrated sunlight immersed in water or continuously splashed with liquids By all means make sure that the module is not s...

Page 11: ...f the module frame if present is not required for fault free operation To reduce the risk of electric shock e g due to static charge as far as possible MegaCell recommends to ask an experienced instal...

Page 12: ...ith the frame Then turn the screw another quarter or half turn The thread cutting screw should be torqued by 20 4 lb in and 24 8 lb in 2 3 and 2 8 Nm Ground wire placement Insert the cable into the wi...

Page 13: ...hould not be mounted in such a way that the drain holes of the module can become blocked MegaCell PV modules are suitable for mechanical mounting both in portrait and landscape orientation In choosing...

Page 14: ...will render the product and performance warranty void 5 2 Frameless modules The use of frameless MegaCell modules requires frameless mounting system that grabs the edge of the module with a pressure...

Page 15: ...snow load zones the terrain category and the height of the building 6 ELECTRICAL INSTALLATION Do not connect or disconnect modules under load Danger Risk of serious injury or death from electric shock...

Page 16: ...ed against reverse polarity o Keep the total area of all conductor loops as low as possible in order to reduce the voltages due to indirect lightning strikes o Always carry out a careful final check o...

Page 17: ...LES MegaCell recommends to inspect the installation on a regular basis with following minimum maintenance o Check the electrical and mechanical connections to verify that they are clean secure and und...

Page 18: ...sual appearance of the module surface and result in decreased performance o Use of automatic cleaning machines for solar energy systems is at your own risk and is not authorized by MegaCell in any way...

Page 19: ...Document name MCELL_PV_Modules_Installation_Manual_EN_v1 2_20150715 Revision date V1 2 July 2015 www megacell it MegaCell S r l a socio unico A coordinated company part of Mega Group S r l Registered...

Reviews: