MANUAL setting. When the auxiliary circuit is full return the lever to the
AUTOMATIC
position.
●
Switch on the boiler, ensure the programmer is set to Hot Water and
allow the cylinder to
heat up to a normal working temperature 65°C (recommended).
Indirect Units (Solar Primary Circuit)
controls.
●
The cylinder temperature control sensor probe supplied with the
solar differential temperature controller must be inserted into the pocket in the
lower controls housing and its cable securely clamped.
●
Heating by the solar
primary circuit is controlled by the solar differential temperature controller,
refer to the manufacturer's installation instructions for details of how to set up
and commission the solar primary circuit.
●
The solar controller should be
programmed to give a maximum storage temperature in the Megaflo eco Solar
of 70°C although 65°C is recommended to minimise scaling
●
WARNING
: If the unit is to be left unused following installation and commissioning, e.g.
unoccupied properties, the water heater should be drained or regularly flushed
through with fresh mains water once a week.
●
When placing the unit into
service, the procedure for filling the unit and the system checks above should be
observed.