M
AINTENANCE
40
Pump symbol on controller
rotates but pump
does not operate
Pump fault – replace pump
Check connections and rectify
as necessary
Free impeller and replace
air bleed screw
Is controller to
pump connection correct
and secure?
Is the pump seized?
Can the impeller
be revolved using a
screwdriver after removing the
air bleed screw?
NO
YES
NO
NO
YES
YES
Water discharge from
temperature and pressure
relief valve
Contact an authorised service
engineer for further advice
Expansion valve not opening at
correct pressure. Replace expansion
relief valve cartridge
Thermal control failure.
Switch off power to all heat sources.
Do not turn off water supply. When
cool check all thermal controls
Is the discharge
intermittent?
Is the discharge
continuous and very hot?
YES
YES
NO
NO
Heating fault –
water may have cooled
Blending valves set too low
Thermostat settings
too low
Water from hot taps is
lukewarm
Contact an authorised service
engineer for further advice
Follow steps as for cold water
Check and adjust if necessary.
Recommended setting – 55ºC
Check and adjust if necessary.
Recommended settings 60-65ºC
YES
YES
YES
NO
NO
NO
Is the discharge
intermittent?
Is the discharge continual?
Is the pressure
reducing valve working
correctly?
Is expansion valve seat
damaged?
Water discharge from
DHW expansion valve
Contact an authorised service
engineer for further advice
Check DHW expansion vessel charge
pressure. Recharge as necessary
Check pressure from pressure
reducer is 3 bar (±0.5 bar).
If not, replace PRV cartridge
Remove expansion valve cartridge
and check seating. If necessary
replace expansion valve
NO
YES
YES
YES
YES
NO
NO