M
AINTENANCE
41
Resistance table PT1000.
The correct function of temperature
sensors can be checked on the basis
of the following temperature resistance
table with a resistance measuring
instrument:
Temperature in °C
Resistance in Ohm
-30
882
-20
921
-10
960
0
1000
10
1039
20
1077
30
1116
40
1155
50
1194
60
1232
70
1271
80
1309
90
1347
100
1385
120
1461
140
1535
200
1758
Displayed temperatures on
controller vary greatly over
short time intervals
Controller fault – replace controller
Sensor fault – replace sensor
Separate sensor cables from mains
cables (min. 50mm recommended)
or use shielded cable
Use shielded cable to extend sensor
cable lengths
Rectify sensor connections
Are sensor cables
laid alongside voltage
cables?
Have
sensor cables been
lengthened with unshielded
cable?
Do sensors
give correct
temperature v resistance
readings?
Are temperature sensor
connections correctly made?
YES
YES
NO
NO
NO
NO
YES
YES
No display at solar differential
temperature controller
Controller fault – replace controller
Connect any wiring faults
Reset thermal cut-out. Investigate
cause of operation and rectify.
NOTE: Allow the cylinder to cool
or draw off the hot water before
resetting
Check wiring and rectify
Replace internal fuse
Switch on power supply
Is the 230/240V~
power supply correctly
wired?
Is the 230/240V~ power
supply switched on?
Is internal fuse operational?
Has thermal cut-out on
cylinder operated?
Is the
230/240V~ power supply
at the controller terminal
bock?
NO
YES
YES
NO
YES
YES
YES
NO
NO
NO