Megatherm wood-pellet burner 

              MPB 90 Pro 

19.

Errors

Indication

Description

Solution / 

Malfunction of the water

temperature sensors

1.   The   driver   starts   up   relevant   emergency
procedures for every sensor in order to prevent
the boiler from working beyond the safe range
for the installation  of the central heating
2.  When the boiler cools down, then restart the
controller   and   set   the   burner   on   automatic
mode.

"Furnace protect" 

The temperature in the

boiler is higher than 92 

o

C.

If the temperature is above

95 

o

C, the STB sensor is

activated and the feeder is

turned off automatically (the
light next to the STB sensor

is ON).

At any case the pumps are

activated to avoid higher

temperatures

1.   Wait till  the boilers  water temperature goes
down to 60 

o

C

2.  Reset the STB sensor, so the light next to it to
be OFF.
3.   Restart the controller and set the burner at
automatic mode.

"Burner alarm" 

The temperatures on

burner's feeder pipe is

higher than 65 

o

C. (Back

fire protection)

This is happened either the

chimney's draught is no the

appropriate or the burner

hasn't been cleaned.

1.

If   the   temperature   goes   down   to   60  

o

C

and   the   photo   sensor   scans   light,   then   the
burner's operation continuous normally.

2.

If   the   temperature   goes   down   to   60  

o

C

and the photo sensor doesn't scan any light,
then  the signal “Burner alarm” is still on the
LCD and you must restart the controller.

"NO pellet" 

1.

No pellet on the silo

1.  Fill up the silo with pellet
2.     Fill   the   feeder   with   pellet   (Filling   feeder
procedure)
3.  Set the burner at automatic mode

2.

The feeder doesn't 
work

If the light next to STB sensor is ON, it means
that overheat of the boiler has occurred and STB
has turned the feeder OFF.
1.  Reset the STB sensor, so the light next to it to
be OFF.
2.   Restart the controller and set the burner at
automatic mode.

Check the cable from feeder to the controller

3.  Problem during 
ignition procedure

Burner's tube hasn't been cleaned properly 
1. Clean the burner
2.   Restart the controller and set the burner at
automatic mode.

Igniter doesn't work
1. Change the igniter inside the burner.

23

CH: !!!!!!            WUW: !!!!!!!

STOP 

Summary of Contents for MPB 150 Pro

Page 1: ...erm wood pellet burner MPB 90 Pro Wood pellet burner MPB 90 Pro Installation User Manual This manual is for the Installer Read understand and follow these instructions for safe installation and operat...

Page 2: ...thermostat 18 11 First use 19 12 Start of the burner 19 13 Stop of the burner 19 14 Cleaning burner s chamber 20 15 Restart the burner after an error 21 16 Feeder s filling rocedure 21 17 Self cleanin...

Page 3: ...and or clothing Always follow the instructions for operations and service Only wood pellets are to be used with this burner No other fuel is to be used in the burner NEVER BURN ANY TYPE OF CORN CHERRY...

Page 4: ...RESIS must be more than 10 o C Continuous mode The burner reaches the desired HEATING WATER TEMPERATURE and goes down at 3kW maintain When the boiler s temperature goes down to the temperature HEATING...

Page 5: ...4 400 77 400Kcal Maximum pellet consumption 8 18kg hr Lenght total 745mm Width 270mm Height with feeding pipe 360mm Height without feeding pipe 290mm Diameter 180mm Power supply 230Volt 80Hz Average p...

Page 6: ...se in the winter heating season 5 Chimney We recommend that you have a local chimney sweeper or other corresponding authority make an inspection and provide advice and instructions on the chimney meas...

Page 7: ...F BUTTONS 1 Changes the burner s working mode STOP IGNITION AUTOMATIC WORK 2 Return to the previous menu 1 Entry on the Menu s parameters 2 Saves the change of a parameter 1 In the Ignition MODE activ...

Page 8: ...0 8A ExternalFeeder 230V 2A 0 8A Internal Feeder 230V 2A 0 8A Burner s fan 230V 2A 0 8A CH pump 230V 2A 0 8A Thermostat 2 contacts open close max 24V 2A Protection Temperature STB 95 C Electric Fuse...

Page 9: ...re of useful warm water of the WUW buffer if the function is active On the screen appears which function is currently used by the driver The driver may work in three working modes STOP IGNITION AUTOMA...

Page 10: ...he mode would be automatically changed after detecting a flame by the sensor CLEANING The cleaning of the burner from he left ashes The cleaning function also as a blow down before ignition WORK Heati...

Page 11: ...URNACE SETTINGS A FUNCTION NO FUNCTION NAME SETTING UNIT SETTING RANGE MANUFACTURER SETTING 1 HEATING WATER TEMPERATURE C 35 85 65 2 CH PUMP ACTIVATION TEMPERATURE C 20 60 35 3 CH FURNACE HYSTERESIS C...

Page 12: ...W maintain to the maximum burner power i e30kW The CH FURNACE HYSTERESIS must be no more than 5 o C Analogue mode The burner reduces its power 1 3 for example from 30kW to 21kW 10 o C before the furna...

Page 13: ...DETECTOR TRESHOLD 5 90 10 10 FURNACE PROTECTION OVERHEAT C 60 90 80 11 STB TEMPERATURE C 90 110 90 12 FEEDER MULTIPLIER 1 5 2 13 IGNITION STABILIZATION Seconds 0 250 30 14 MAINTAIN STABILIZATION Seco...

Page 14: ...sions of the driver Description of manufacturer s settings 1 FEEDER FILLING TIME In this menu the manufacturer sets the time of the feeder s filling The time is the protection from filling up of the b...

Page 15: ...he step of 500grams Manufacturer Advise Can not be given any advise since it is depended on the feeder s angle and pellet quality Please follow the procedure on paragraph 11 First use 6 PELLETS FEEDIN...

Page 16: ...higher temperature than the one that was previously set is reached and when the CH pump is turned off The driver starts the CH pump automatically and switches off the burner The protection of the furn...

Page 17: ...h is located in the burner s fire chamber before starts the maintain mode Manufacturer Advise 60 240sec 15 MAXIMUM BURNER POWER In this parameter the installer can set the maximum burner power where t...

Page 18: ...ostat is ON the burner works at the maximum power it is set 2 When thermostat is OFF the burner goes at maintain mode and keeps a small fire In both cases when the thermostat is OFF the CH pump stops...

Page 19: ...g after the first pellets come out of the feeder for 10 15 minutes locate a plastic bag at the exit of the feeder 5 Empty the plastic bag and place it back at the exit of the feeder 6 Connect again th...

Page 20: ...n the boiler s water temperature reaches the desired temperature HEATING WATER TEMPERATURE the the power of the burner goes down ta 3kW Maintain mode 7 The burner works at Maintain mode till the boile...

Page 21: ...burner after an error 1 Turn off the burner by pressing the button ON OFF 2 Open the boiler s door and check the burners tube 3 Remove any ashes and impurities from burners tube 4 Close the door and s...

Page 22: ...ms For total fail safe security the burner is equipped with four safety systems 1 The plastic pipe connecting the feeder with the burner This tube will melt away from the burner in event of a too high...

Page 23: ...n 65 o C Back fire protection This is happened either the chimney s draught is no the appropriate or the burner hasn t been cleaned 1 If the temperature goes down to 60 o C and the photo sensor scans...

Page 24: ...Megatherm wood pellet burner MPB 90 Pro 20 Electrical diagram REG 03 2C 24...

Page 25: ...metal parts 2 years in electric parts feeder s motor air fan 1 year in electronic controller No waarranty is given for the heating element igniter Pellet heating systems Vasilika Thessaloniki 57006 G...

Reviews: