Wood-pellet burner
Nani 35
3.
FAN POWER (IGNITION)
In this parameter the producer sets the power of the fan during the pellet's ignition. The
fan's power is set in the bracket of 5 to 50%.
If chimney's draught is over -15Pa, then the parameter stays at 10%
If chimney's draught is from 0 to -15Pa, then the parameter must change to 15-20%.
Manufacturer Advise:
10-15%
4.
PELLETS DOSE (IGNITION)
In this parameter the manufacturer sets the dose of fuel needed to ignite the burner. The
parameter is set in the bracket of 50 to 500 grams. Depending the pellet's quality the
parameter can change from 150gram to 220grams. The default value is
200grams
Manufacturer Advise:
180-240gr
. Depends on pellet quality and on momentum the
pellet comes into the burner
5.
FEEDER PERFORMANCE
In this parameter the manufacturer sets the performance of the feeder. The whole work of
the burner is based on this parameter. The parameter is set in the bracket of 5 to 45 kg/h
with the step of 500grams.
Manufacturer Advise:
Can not be given any advise since it is depended on the
feeder's angle and pellet quality. Please follow the
procedure on paragraph 11 “First use
6.
PELLETS FEEDING PERIOD
In this parameter the manufacturer sets the period of feeding the pellet. After the lapse of
time, the driver releases the next dose of fuel. In the cycle of maintain, the parameter is
ten times multiplied. The feeding period of the pellet is set in the bracket of 10 to 60
seconds.
Manufacturer Advise:
10-20s
7.
OVERFLOW PELLETS AIR (WORK)
In this parameter the manufacturer sets the overflow of the air needed to burn the
specified amount of the pellet when the burner works at full power.. This parameter should
be increased if during the working cycle too low capacity of the fan would be noticed. The
overflow of the air is set in the bracket from 0.2 to 4.
Depending on the burner's maximum power ,pellet's quality, boiler's construction
and chimney's draught, the paramater will be set between 0.20-0.6
14