Manual RLC Test
Use this screen to manually execute Resistance, Inductance, and Capacitance tests. Elements within the screen provide
control over how the tests are executed.
Icons at top right include test configuration access, save, help, and exit screen.
The screen header displays the test type being conducted, along with the Asset selected and the active Test
Configuration for the selected Asset.
In manual mode, the software will use limits specified in the Test Configuration, but you directly specify test parameters
such as the Imbalance Calculation to use, Temperature Compensation parameters, and which tests to enable.
NOTE: Changes made here only affect the current testing session and will not be permanently saved
to the selected test configuration.
From this screen, you can make the following adjustments if needed:
Select the Imbalance Calculation to use during resistance, inductance, and impedance testing by using the
Imbalance Calculation drop-down list.
Select which tests you want to run by moving the toggles to the right.
For temperature compensation, select the winding conductor material using the associated drop-down list then
enter the Actual and Correct To values as needed.
Fig 42:
Manual Test—RLC start screen.
1. After completing your specifications, press the individual Lead tests that you want to run, or press ALL LEADS.
www.megger.com/baker
Megger Baker ADX Quick Reference Guide
42
Procedures for Testing with the ADX Analyzer