7. You can use the Y/DELTA tab to view additional test details that can help you identify which winding is causing the
test to fail. After all three L-L values are directly measured, a software algorithm calculates the values for each phase
in both wye and delta configurations for the motor, and presents them in this tab.
Refer to the
Megger Baker ADX User Guide
for more information on interpreting the results displayed in this tab.
Fig 45:
Manual Test—RLC Y/Delta tab.
NOTE: RLC test results can be saved or overwritten with a retest while still in this testing session.
8. When you have completed your examination of the test results, touch the Save icon to save your results to the ADX
database.
9. Touch the Exit icon to leave the RLC test screen and return to the Manual Tests main screen.
www.megger.com/baker
Megger Baker ADX Quick Reference Guide
44
Procedures for Testing with the ADX Analyzer