Megger Limited
PWS / Nov 06
DET4TC/R Launch
25
This makes this method particularly suited to measuring lighting protection systems
on buildings. Normally the time consuming practice of removing test links would be
required, and a 2-pole test applied.
The normal 2-pole method would be applied as follow:
Using the stakeless method negates the requirement to remove these links, just
clamp the
ICLAMP
and
VCLAMP
around the tape or link.
Incorrect use of Stakeless testing
The stakeless method is not unfortunately, to coin a phrase, miss-stakeless. As with
the
ART
method, test current must go through the earth mass to be able to measure
the earth resistance. Used incorrectly the method may give misleading results.
Removable links
(Jug handles)
Link removed for
2 pole measurement
Lightning protection tape
Test current flowing around loop
Of lighting protection tape.
Lightning protection tape