Pinpointing Sheath Faults in „ESG“ Mode
86
Step Action
6
Place the black earth spike on the suspected position of the fault and the red
earth spike about one metre away. The signal must now point in the direction of
the black earth spike. Repeat this control measurement at several other
positions in a circle around the black earth spike.
If the signal level indicates towards the black earth spike at each control
measurement, the fault position has been successfully verified.
7
Repair the damaged section and test the sheath again for any further damage.
6.3
Completing the Work
After the sheath fault has been successfully pinpointed, the indicator unit can be turned
off by pressing the
button
for 3 seconds
.
Afterwards, the DC impulse generator can be switched off and disconnected from the
cable under test while making sure that all applicable safety regulations are followed.