SETTING UP
AVTMMIT30-EN Rev E02 June 2009
17
CONNECTION PROCEDURE
1.
Ground and bond all terminals of the test
object to a known, good earth ground point.
2.
With the test set switch off, connect the
power cord to the mains supply.
WARNING
The third wire in the input power
line is the system ground.
Operator and equipment safety
depend on this connection
being made to a good ground.
3.
Connect BLUE guard lead to drain leakage
currents. (See USE OF GUARD section)
4.
Connect BLACK current sense lead to the
low potential end of the test object.
5.
Connect RED output cable clip to the high
voltage terminal of the apparatus to be tested