If the power lead supplied is not suitable for your type of mains outlet, do
not use an adaptor. Always use a power lead fitted with the correct plug.
NB
: A plug severed from the power lead is a hazard if plugged into a live
socket. Severed plugs must be destroyed immediately.
The instrument is fitted with a two-pin IEC60320 power inlet. Most power
leads are made with three-core cable so the ground connection will not
be used.
Power lead cable colour coding:
International
USA
Earth/Ground
Yellow/Green
Green
Neutral
Blue
White
Live (Line)
Brown
Black
If using a fused plug ensure it is fitted with a 3 Amp fuse.
The instrument can be powered from 95 - 240 V rms, ±10% 50/60Hz.
With power connected the battery will charge as long as a test is not in
progress. The
Power On/Off
button has a green LED which illuminates
when mains power is present.
For best battery lifetime, charge the battery after each use. A completely
exhausted battery will take 14 hours to recharge.
INTRODUCTION
POWER LEAD AND CHARGING
4
The MIT510/2 is a compact microprocessor controlled high voltage d.c.
insulation tester, powered by internal rechargeable battery or mains
supply. A comprehensive LCD display shows resistance, current,
capacitance, voltage and timer measurements digitally, with resistance
being shown in analogue as well.
Features include:
n
Resistance or current measurement- front panel selectable
n
Resistance measurement range - 10 k
Ω
to 15 T
Ω
n
Front panel selectable test voltages - 250 V, 500 V, 1000 V, 2500 V, 5000 V
n
Incremental timer (minutes & seconds) – measures during test
n
Load capacitance measurement – displayed at end of a test
n
LCD backlight – front panel selectable
n
Battery level/charging indicator
n
Mains (line) input presence LED
n
High voltage warning flashing LED shows when greater than 50 V
present on test leads
n
High voltage warning LCD "flash" shows when greater than 50 V
present on test leads
n
8 hours continuous testing on full charge.