background image

The guard terminal is at the same potential as the negative terminal. Since

the leakage resistance is effectively in parallel with the resistance to be

measured, the use of the guard causes the current flowing through surface

leakage to be diverted from the measuring circuit. The instrument

therefore reads the leakage of the insulator, ignoring leakage across its

surface. The display will show ‘FUS’ if the internal guard terminal fuse is

found to have blown. The instrument must be switched off to clear the

message before further testing is permitted. The fuse should be replaced

by an authorised repairer. The instrument may be used in the mean time if

the guard terminal not used. Refer to notes regarding measurements

above 100 G

on page 9.

Factory programming socket

This is a 9 pin socket under the hinged cover and is not for customer use.

Line input present LED

This is a green LED next to the power On/Off button on the front panel. It

is illuminated whenever the mains power is connected.

Test terminals

There are three test terminals , - and G. These terminals are

designed to accept only the test leads supplied. Shutters across the

terminals prevent accidental ingress of dirt and other objects. Test lead

plugs interlock with the shutters and are released by rotating the test lead

plug a quarter turn.

The Guard terminal is explained below and is only used in cases where

surface leakage currents need to be eliminated. Most measurements use

just the + and – terminals. The instrument’s internal voltage generator

drives the + terminal with respect to the – terminal, current being

measured in the – terminal.

Guard terminal

For basic insulation tests and where there is little possibility of surface

leakage affecting the measurement, it is unnecessary to use the guard

terminal i.e. if the insulator is clean and there are unlikely to be any adverse

current paths. However in cable testing for example, there may be surface

leakage paths across the insulation between the bare cable and the external

sheathing due to the presence of moisture or dirt. Where it is required to

remove the effect of this leakage, particularly at high testing voltages, a

bare wire may be bound tightly around the insulation and connected via

the third test lead to the guard terminal ‘G’.

7

Summary of Contents for MIT510/2

Page 1: ...M MIT510 2 5kV Digital Insulation Tester USER MANUAL...

Page 2: ...d items should be firmly shorted out with a shorting link after discharge until required for use This is to guard against any stored dielectric absorption charge subsequently being released thereby ra...

Page 3: ...ndicate best practice Cleaning Disconnect the instrument and wipe it with a clean cloth slightly damped with soapy water or Isopropyl alcohol IPA CONTENTS 3 Safety warnings 2 Cleaning 3 Introduction 4...

Page 4: ...harge the battery after each use A completely exhausted battery will take 14 hours to recharge INTRODUCTION POWER LEAD AND CHARGING 4 The MIT510 2 is a compact microprocessor controlled high voltage d...

Page 5: ...t first will perform a self check during which Ini is displayed After Ini disappears the instrument is ready for use 3 Check voltage at terminals display to be sure the load is safe to energise 4 Set...

Page 6: ...played briefly When the test has stopped the display continues to show the voltage present on the test leads Pressing either test voltage s or t button will then display the test voltage immediately b...

Page 7: ...rminals marked and G These terminals are designed to accept only the test leads supplied Shutters across the terminals prevent accidental ingress of dirt and other objects Test lead plugs interlock wi...

Page 8: ...display shows the last measurement made until the timer or voltage test settings are changed or the test start stop button is pressed Analogue display This simulates an analogue meter movement to give...

Page 9: ...en the positive and negative terminals These leakages have a significant effect and can occur through the air itself If the guard lead is connected to ground then since the negative terminal is at the...

Page 10: ...rt circuit charge current 3 mA 5 kV Capacitor charge time 3 seconds per F at 3mA to 5 kV Capacitor discharge time 120 ms per F to discharge from 5000 V to 50 V Capacitance measurement 500 V minimum te...

Page 11: ...nA at all voltages Interference rejection 1 mA rms per 250 V test voltage up to a maximum of 2 mA Timer range Counts up to 99 minutes from start of test Test regimes Auto IR Lead set Three flexible si...

Page 12: ...insulated small clips 8101 183 3 x 10 m with medium insulated clips 1000 441 3 x 15 m with medium insulated clips 1000 442 3 x 3 m with large insulated clips 6220 811 3 x 10 m with large insulated cl...

Page 13: ...or your Megger products Returning your product to Megger UK and USA service centres 1 When an instrument requires recalibration or in the event of a repair being necessary a Returns Authorisation RA n...

Page 14: ...2 Canada T 1 416 298 9688 Canada only T 1 416 298 6770 F 1 416 298 0848 E casales megger com Megger 501 Crystal Paradise Mall Off Veera Desai Road Andheri w Mumbai 400053 Maharashtra India T 91 22 267...

Reviews: