INSTRUMENT CONTROLS AND INDICATORS
Power On/Off button:
The instrument will only turn on if this button is pressed, held and then
released after the display responds.
If pressed and released before the display responds the instrument will
not turn on.
If pressed and held continuously the instrument will not turn on.
This sequence is a safety feature to prevent the instrument inadvertently
turning on.
To power the instrument down at any time, press
Power On/Off
again.
The instrument will also power down after 10 minutes of inactivity.
Once powered, the display will first show
Ini
while it does a self-check.
When
Ini
disappears, the instrument is ready for use.
V
▲
and V
▼
buttons:
Using these buttons one of five test voltages can be selected: 250 V,
500 V, 1000 V, 2500 V or 5000 V. The selected voltage is shown on the
display.
If there is an external voltage greater than 50 V on the test leads the
display will show this voltage instead. The instrument will not do a test if
this is the case.
After a test has started, the display shows the voltage on the test leads
only. If the test voltage is changed during a test, the new test voltage will
be displayed briefly before the display again shows the voltage on the test
leads.
After a test has been stopped, the display shows the test voltage selected
once the load has discharged to below 50 V.
TEST button:
A test will only start if this button is pressed, held and then released as
soon as the red HV LED lights. When the test starts the red HV LED flashes
and the display flashes the HV warning symbols.
If pressed and released before red LED shows a test will not start.
If pressed and held continuously the instrument will immediately stop the
test.
This sequence is a safety feature to prevent the instrument inadvertently
starting a test.
If an external voltage greater than 50 V is present on the test leads, this
will be shown by the red HV LED and the display HV warning symbols
flashing. Testing will be disabled until this voltage falls below 50 V.
Testing will stop if the
TEST
button is pressed again.
After a test has finished, the instrument will discharge the load which may
take some time. Always check the load has been discharged before
touching the test leads.
Ω
/I button:
Pressing this button toggles the digital display between the insulation
resistance and current.
6