Annex 1: Measuring Accuracy
31
Voltage
Operating uncertainty
Current and measuring range
115 V
3% ± 1 mΩ
≥ 200 A for |Z| > 10 mΩ
100 A for |Z| > 200 mΩ
80 A for |Z| > 500 mΩ
5% ± 1 mΩ
100 A for 40 mΩ < |Z| < 200 mΩ
80 A for 150 mΩ < |Z| < 500 mΩ
10% ± 1 mΩ
100 A for 10 mΩ < |Z| < 40 mΩ
80 A for 30 mΩ < |Z| < 150 mΩ
230 V
3% ± 1 mΩ
≥ 400 A for |Z| > 10 mΩ
300 A for |Z| > 45 mΩ
200 A for |Z| > 150 mΩ
100 A for |Z| > 300 mΩ
80 A for |Z| > 500 mΩ
5% ± 1 mΩ
300 A for 10 mΩ < |Z| < 45 mΩ
200 A for 45 mΩ < |Z| < 150 mΩ
100 A for 200 mΩ < |Z| < 300 mΩ
80 A for 275 mΩ < |Z| < 500 mΩ
10% ± 1 mΩ
200 A for 20 mΩ < |Z| < 45 mΩ
100 A for 80 mΩ < |Z| < 200 mΩ
80 A for 180 mΩ < |Z| < 275 mΩ
400 V
3% ± 1 mΩ
≥ 600 A for |Z| > 10 mΩ
500 A for |Z| > 25 mΩ
400 A for |Z| > 70 mΩ
300 A for |Z| > 190 mΩ
200 A for |Z| > 400 mΩ
100 A for |Z| > 600 mΩ
5% ± 1 mΩ
500 A for 10 mΩ < |Z| < 25 mΩ
400 A for 10 mΩ < |Z| < 70 mΩ
300 A for 90 mΩ < |Z| < 190 mΩ
200 A for 180 mΩ < |Z| < 400 mΩ
100 A for 525 mΩ < |Z| < 600 mΩ
80 A for 600 mΩ < |Z|
10% ± 1 mΩ
300 A for 20 mΩ < |Z| < 90 mΩ
200 A for 50 mΩ < |Z| < 180 mΩ
100 A for 300 mΩ < |Z| < 525 mΩ
80 A for 500 mΩ < |Z| < 600 mΩ