4. If the display window is to freeze the voltage
reading at trip/signal time, check to see
that the HOLD function is active (it can be
activated by means of the HOLD button).
5.
If the 0-250 V AC output is considered not
sensitive enough, one of the following
outputs can be selected: 0-10, 0-40 or
0-100 A. Alternatively, the voltage can be
divided by means of the set of resistors
included with the Sverker.
Pick-up and drop-out functions: U <
ON and U < OFF
1. Turn on the Sverker current source by acti-
vating ON with the start switch (press the
W
key once), whereupon the ON indicator
lamp will light.
2. Increase the voltage to 1.1-1.2 x the relay
voltage setting.
3. Decrease the voltage until operation occurs
(U < ON), whereupon the Sverker TRIP
indicator will start to glow steadily.
4. Read the
U < ON
value from the display
window.
5. If the freeze function has been activated,
press the HOLD button twice to unfreeze
the value shown.
6. Increase the voltage until drop-out takes
place (U < OFF), whereupon the TRIP
indicator will be extinguished.
7. Read the U < OFF value from the display
window.
Operating time: U < ON + TIME
DELAY
1. Turn on the Sverker main source by setting
the start switch to the ON position, where-
upon the ON indicator lamp will light.
2. Increase the voltage to 1.1-1.2 times the
relay voltage setting (1.1-1.2 x U < ON).
3. Activate OFF + TIME using the start switch
(press the
W
key), whereupon the main
source stops to generate voltage and the
timer starts .
4. When the protective relay equipment oper-
ates, the time stops automatically, where-
upon the TRIP indicator starts to flash.
5. Read the
U < ON + TIME DELAY
value from
the display window.
6. Repeat the U < ON + TIME DELAY run two or
three times to confirm its accuracy through
repetition.
Finishing the test
1.
Enter the values read from the display into
the test report.
2.
Turn off power to Sverker using the mains
switch.
3.
Disconnect the equipment.
Summary of Contents for Programma Sverker 750
Page 1: ...SVERKER 750 760 User s manual Relay Test Unit ...
Page 28: ...2 9 S V E R K E R 7 5 0 7 6 0 P r o g r a m m a E l e c t r i c A B Z P C D 0 1 E R 0 5 A ...
Page 75: ...7 6 S V E R K E R 7 5 0 7 6 0 P r o g r a m m a E l e c t r i c A B Z P C D 0 1 E R 0 5 A ...
Page 76: ...Subject to change without notice Printed matter ZP CD01E R05B 2007 ...