RCD type selection

To select the RCD type to be tested:

1. Set the top RCD selection knob (top knob) to the desired RCD current

range.

2. Set the RCD test knob to 1/2I, I or 5I as required.

3. Press the [TYPE] button to select the type of RCD under test:

Options are:

AC Standard

AC Selective

DC Sensitive

DC Selective

I RCD (Non-tripping) measurement 

To test the tripping time of the installed RCD under test:

Range selection:

1. Connect the mains plug test lead or 2-wire Red/Green test lead to the 

instrument.

2. Plug in the mains plug test lead to the wall outlet, or the 2 wire test

lead across the RCD (refer to connection drawing in section 4.2)

3. Set the top RCD selection knob to the correct range for the RCD

under test.  

4. Set the bottom range knob to [1/2I]. The RCD trip indicator should

display a closed symbol 

.

5. Ensure the display shows the mains voltage.

6. Press the  [TEST] button. The instrument should display >1999ms and

the RCD should NOT trip.

12

NOTE:

If the RCD should trip while performing a 1/2I test the error

message ‘

trP

’ will be displayed instead of the time display.

1xI  RCD trip time measurement

To test the [1xI] trip time of the installed RCD:

1. Repeat the previous test for 

I, but with the bottom range knob set to

I. The RCD trip indicator should display an open symbol 

.  

2. The instrument should display the RCD trip time in milliseconds.

If the display shows >200 ms the RCD has failed to trip in the
appropriate time. Check your test lead connections to the RCD and
repeat the test.

If the RCD still fails to trip, suspect a faulty RCD.

Note:

See also 0°/180° testing below.

0° or 180° testing

Both the [1 x I] and [5 x I] tests should be performed for 0° and 180°.

Repeat the 1 x I and 5 x I tests as above but with the instrument set to
180°.

0° or 180° is selected by pressing the [0°/180°] and the greatest trip time
for each test recorded.

RampTest 

The RCD trip current is measured by applying a test current of half the
rated trip current and increasing this every 200ms. When the RCD trips,
the current flowing is recorded and displayed in mA.

RCDT300_UG_en_V01  07/05/2004  12:07 pm  Page 12

Summary of Contents for RCDT300 Series

Page 1: ...M RCDT300 Series Residual Current Device testers USER MANUAL RCDT300_UG_en_V01 07 05 2004 12 07 pm Page 1...

Page 2: ...ged Test leads probes and crocodile clips must be in good order clean and with no broken or cracked insulation The battery cover must be in place whilst conducting tests Voltage indicator LED s cannot...

Page 3: ...the carton 5 LCD Display 6 Top panel 6 Lid open closure 17 Preparations for use 8 Batteries 8 Preliminary test lead check 8 General operating instructions 8 Display warning symbols 9 Setup procedure...

Page 4: ...ent test RAMP 0 180 polarity selection Selective breakers INTRODUCTION GENERAL DESCRIPTION 4 Thank you for purchasing the Megger RCD Tester For your own safety and to get the maximum benefit from your...

Page 5: ...RCDT320 1 x RCDT300 series RCD tester 1 x 3 wire test lead with prods with clips 8 x AA LR6 batteries fitted in instrument 1 x Test lead case 1 x Warranty card 1 x Calibration certificate 1 x Owners C...

Page 6: ...0mA RCDT320 only 30mA 100mA 300mA 500mA 1000mA RCDT320 only Neck strap slots Test selector x I RCD trip time 1 x I RCD trip time 5 x I RCD trip time AUTO RCDT320 only Ramp RCDT320 only V AC DC volts R...

Page 7: ...taining slot 4 Connection Panel RCDT300 Series test lead connections 7 Mains plug test lead connector Single or 3Phase connection Neutral or 2nd phase connection Warning Refer to User Guide Maximum 30...

Page 8: ...ator will be displayed Default voltmeter The default voltmeter automatically operates in all test modes indicating connection to a live system Auto Power down To extend battery life the instrument wil...

Page 9: ...ble on the instruments as per the relevant tables in the specification section of this document Reverse polarity detection Touch voltage setting To select Polarity reversal acceptance or rejection 1 W...

Page 10: ...the TEST button to exit from the set up menu Test leads All test leads form part of the measuring circuit of the instrument and must not be modified or changed in any way or be used with any other ele...

Page 11: ...ING 11 Method of measurement The plug ended test lead or two wire lead should be used for this measurement A constant current source is connected across the supply and the time taken for the supply to...

Page 12: ...p 12 NOTE If the RCD should trip while performing a 1 2I test the error message trP will be displayed instead of the time display 1xI RCD trip time measurement To test the 1xI trip time of the install...

Page 13: ...RCDs these should be tested at 0 and 180 or in the case of DC sensitive RCD s positive or negative Possible sources of error Measurement results can be affected by the following 1 Significant operatin...

Page 14: ...a lower charge than Alkaline batteries and my not give much warning before becoming exhausted To replace batteries Warning Do not switch the instrument on with the battery cover removed 1 Switch off t...

Page 15: ...hould not be left in an instrument which may remain unused for extended periods Fuse Blown indication The fuse blown symbol f indicates that an internal fuse has failed This instrument is fitted with...

Page 16: ...indicates which Megger RCD300 series testers feature the Touch voltage inhibit feature RCD Testers Line reversal detection Inhibit available Y N Y N English language RCDT310 EN AU No No RCDT320 EN AU...

Page 17: ...All units 980gms Dimensions All units 203 x 148 x 78 mm E M C In accordance with IEC61326 including amendment No 1 17 SPECIFICATION RCD Test Ranges to EN61557 6 Test Current Accuracy No Trip Test I 8...

Page 18: ...y voltage temperature interference and system voltage and frequency where applicable 18 BASIC AND SERVICE ERRORS ACCESSORIES AND EQUIPMENT Item Order Code 2 wire test lead set and crocodile clips 6220...

Page 19: ...Archcliffe Road Valley Forge Corporate Centre Dover 2621 Van Buren Avenue Kent CT17 9EN Norristown PA 19403 England U S A Tel 44 0 1304 502 243 Tel 1 610 676 8579 Fax 44 0 1304 207 342 Fax 1 610 676...

Page 20: ...20 RCDT300_UG_en_V01 07 05 2004 12 07 pm Page 20...

Page 21: ...21 RCDT300_UG_en_V01 07 05 2004 12 07 pm Page 21...

Page 22: ...22 RCDT300_UG_en_V01 07 05 2004 12 07 pm Page 22...

Page 23: ...23 RCDT300_UG_en_V01 07 05 2004 12 07 pm Page 23...

Page 24: ...0 1 30 16 08 90 F 33 0 1 34 61 23 77 OTHER TECHNICAL SALES OFFICES Toronto CANADA Sydney AUSTRALIA Mumbai INDIA Madrid SPAIN and the Kingdom of BAHRAIN Megger products are distributed in 146 countrie...

Reviews: