M
AVTMTTR25 Rev C April 2008
54
Table C-3 CEI/IEC 76-1:1993 Transformer Winding Phase Relationship
Copyright 1999
©
Megger
Winding Connection
Winding Tested
Diag
No.
IEC
Vector
Group
High-Voltage
Winding
Low-Voltage
Winding
Phase
Tested
External
Jumpers
High-
Voltage
Winding
Low-
Voltage
Winding
Measured
Turn Ratio
1
1
φ
1ph0
1
φ
⎯
1.1-1.2
2.1-2.2
U1
U2
2
1
φ
1ph6
1
φ
⎯
1.1-1.2
2.2-2.1
U1
U2
3
Dd0
U
V
W
⎯
⎯
⎯
1U-1V
1V-1W
1W-1U
2U-2V
2V-2W
2W-2U
U1
U2
4
Dd2
U
V
W
⎯
⎯
⎯
1U-1V
1V-1W
1W-1U
2W-2V
2U-2W
2V-2U
U2
U1
5
Dd4
U
V
W
⎯
⎯
⎯
1U-1V
1V-1W
1W-1U
2W-2U
2U-2V
2V-2W
U1
U2
6
Dd6
U
V
W
⎯
⎯
⎯
1U-1V
1V-1W
1W-1U
2V-2U
2W-2V
2U-2W
U1
U2
7
Dd8
U
V
W
⎯
⎯
⎯
1U-1V
1V-1W
1W-1U
2V-2W
2W-2U
2U-2V
U1
U2
8
Dd10
U
V
W
⎯
⎯
⎯
1U-1V
1V-1W
1W-1U
2U-2W
2V-2U
2W-2V
U1
U2