Appendix C
AVTMTTR25 Rev C April 2008
59
Table C-3 CEI/IEC 76-1:1993 Transformer Winding Phase Relationship
Copyright 1999
©
Megger
Winding Connection
Winding Tested
Diag
No.
IEC
Vector
Group
High-Voltage
Winding
Low-Voltage
Winding
Phase
Tested
External
Jumpers
High-
Voltage
Winding
Low-
Voltage
Winding
Measured
Turn Ratio
33
YNyn6
U
V
W
⎯
⎯
⎯
1U-1N
1V-1N
1W-1N
2N-2U
2N-2V
2N-2W
U1
U2
34
YNy6
U
V
W
1V-1N
1W-1N
1U-1N
1U-1N
1V-1N
1W-1N
*-2U
*-2V
*-2W
U1
U2
35
Yyn6
U
V
W
⎯
⎯
⎯
1U-1V
1V-1W
1W-1U
2V-2U
2W-2V
2U-2W
U1
U2
36
Yy6
U
V
W
⎯
⎯
⎯
1U-1V
1V-1W
1W-1U
2V-2U
2W-2V
2U-2W
U1
U2
37
Yzn1
U
V
W
⎯
⎯
⎯
1U-1W
1V-1U
1W-1V
2U-2N
2V-2N
2W-2N
U1
3
U2
•