M
AVTMTTR25 Rev C April 2008
60
Table C-3 CEI/IEC 76-1:1993 Transformer Winding Phase Relationship
Copyright 1999
©
Megger
Winding Connection
Winding Tested
Diag
No.
IEC
Vector
Group
High-Voltage
Winding
Low-Voltage
Winding
Phase
Tested
External
Jumpers
High-
Voltage
Winding
Low-
Voltage
Winding
Measured
Turn Ratio
38
Yz1
U
V
W
1V-1W
1W-1U
1U-1V
1U-(1V+1W)
1V-(1W+1U)
1W-(1U+1V)
2U-2V
2V-2W
2W-2U
U1
U2
•
3
2
39
Yzn5
U
V
W
⎯
⎯
⎯
1U-1V
1V-1W
1W-1U
2N-2U
2N-2V
2N-2W
U1
3
U2
•
40
Yz5
U
V
W
1V-1W
1W-1U
1U-1V
1U-(1V+1W)
1V-(1W+1U)
1W-(1U+1V)
2W-2U
2U-2V
2V-2W
U1
U2
•
3
2
41
Yzn7
U
V
W
⎯
⎯
⎯
1U-1V
1V-1W
1W-1U
2V-2N
2W-2N
2U-2N
U1
3
U2
•
42
Yz7
U
V
W
1V-1W
1W-1U
1U-1V
1U-(1V+1W)
1V-(1W+1U)
1W-(1U+1V)
2V-2U
2W-2V
2U-2W
U1
U2
•
3
2