24
time
P08.18
Anti-rever
se
selection
Anti-reverse
selection
0: Reverse operation is allowed
1: Reverse operation is prohibited
(run at zero frequency upon
reverse running command)
1 0
×
√
×
P08.19
FWD/REV
dead-
time
FWD/REV
dead- time
0.00~360.00s 0.01s
0.00s
×
√
○
P08.20
FWD/REV
switching
mode
FWD/REV
switching
mode
0: Switch once over the zero
frequency
1: Switch once over the startup
frequency
1 0
×
√
×
P08.21
Use ratio
of
dynamic
braking
Use ratio of
braking
0.0~100.0%(0: Disabled)
0.1
%
100.0
%
×
√
○
P08.22
Braking
startup
voltage
Braking
startup
voltage
660~780 1
700
×
√
○
P08.23
Decelerati
on time
for
emergenc
y stop
Deceleration
time for
emergency
stop
0.00~100.00s (0: Automatic
high-speed deceleration)
0.01s 0.00s
×
√
○
Group P09: Digital input/output parameters
P09.00~
P09.07
Function
selection
of input
terminals
X1~X8
X1 ~ X8
terminal
functions
0: No function
1: Forward running (FWD)
2: Reverse running (REV)
3: External jog forward running
control input
4: External jog reverse running
control input
5: Three-wire operation control
6: Multi-stage reference terminal
1
7: Multi-stage reference terminal
2
8: Multi-stage reference terminal
3
9: Multi-stage reference terminal
4
10: Acceleration/deceleration time
terminal 1
11: Acceleration/deceleration time
terminal 2
16: External fault normally open
input
17: External fault normally closed
1
1
2
6
7
8
0
0
0
√
√
×