DIP switch S1 settings
Tel: +972-3-9626462
Fax: +972-3-9626620
support@meitavtec.com
ETNC24-SUPER-MDB-01
Owner’s manual & Technician Settings
Pg. 8
Important: Disconnect power to the unit before changing the
configuration of the DIP switches.
Using the internal temperature sensor or connect an
external sensor to T-To terminals
Internal sensor (default)…….... S1.1 On
S1.2 Off S1.3 On
External sensor…………..…….S1.1 Off
S1.2 On S1.3 Off
On
1 2 3 4 5 6
Default position:
ON
123456
ON
123456
S2
S1
Heat pump (Active in Cool or in Heat)
or Non Heat pump (Electrical or Oil heaters)
Non Heat pump with El. heaters (default)... S1.4 Off S1.5 Off
Non Heat pump with Oil heaters ………….. S1.4 Off S1.5 On
Heat pump system active in Heat…....……. S1.4 On S1.5 Off
Heat pump system active in Cool…………..S1.4 On S1.5 On
Window contact operation (when closes)
Use Economy set points (default)….....……S1.6 On
Turn the unit Off ……………………..……… S1.6 Off
ON
1 2 3 4 5 6
External sensor
ON
1 2 3 4 5 6
Internal sensor
ON
1 2 3 4 5 6
ON
1 2 3 4 5 6
ON
1 2 3 4 5 6
ON
1 2 3 4 5 6
Non Heat pump
With El. heaters
Non Heat pump
With Oil heaters
Heat pump
Active in Heat
Heat pump
Active in Cool
ON
1 2 3 4 5 6
ON
1 2 3 4 5 6
Economy
set points
Turn unit
Off
S1