Technician Settings (Cont’)
P170 – Economizer low limit temperature
Range: 9...27ºC / 48...80ºF
Default: 17ºC / 63ºF
P186 – Enable/Disable internal PIR
“00” - Disable internal PIR
“01” - Enable Internal PIR
P160 – Minimum compressor ON time (AC Only!)
Range: 0...20 minutes
Default: 2 minutes
Minimum compressor
ON time
P161 – Minimum compressor OFF time (AC Only!)
Range: 0...20 minutes
Default: 13 minutes
Minimum compressor
OFF time
- 54 -
Economizer low
limit temperature
(°F)
(°C)
Enable internal
PIR
Disable internal
PIR
P122 – Cool Proportional output threshold time (FC Only!)
Range: 0...100 seconds
Default: 60 seconds
P123 – Heat Proportional output threshold time (FC Only!)
Range: 0...100 seconds
Default: 60 seconds
Cool proportional
threshold time
Heat proportional
Threshold time