Technician Settings (Cont’)
P192 – Temperature set-point for re-heat in unoccupied mode
Range: 10...30ºC / 50...86ºF
Default: 15ºC / 59ºF
P194 – Humidity differential band
Range: 0...10 %RH
Default: 5%RH
Humidity differential
band
P189 – Dehumidification cycle in unoccupied mode
Range: 0...600 minutes
Default: 20 minutes
P190 – Dehumidification break time in unoccupied mode
Range: 0...900 minutes
Default: 40 minutes
Dehumidification
cycle in unocc. mode
Dehumidification
break in unocc. mode
Set-point for reheat
in unocc. mode
(°F)
(°C)
P187 – Display or hide humidity reading
“00” - Do not display humidity reading
“01” - Display humidity reading
P188 – Room temperature limit for disabling dehumidification in
unoccupied mode
Range: 10...30ºC / 50...85ºF
Default: 18ºC / 64ºF
Display or hide
humidity readings
Temp. for disabling dehum.
In unocc mode
(°F)
(°C)
- 55 -