Temperature reading errors
Tel: (856) 2882882
Tel: +972-3-9626462
Fax: +972-3-9626620
support@meitavtec.com
PYROCON12
Owner’s manual & Technician Settings
Pg. 14
Ambient temperature sensor readings (on snow sensor)
are out of reliable measuring range
Ambient temperature < -9°F/-23°C
Ambient temperature > 54°F/12°C
Upper limit
temperature
Sensor error
Error 2 – Upper limit temperature sensor is not connected or short circuit
“SensErr 2” Will appear on display.
The system will continue to operate regardless of the upper limit temperature.
Required actions:
1. Refer to P03 section of the technician settings.
2. Check the temperature value and disable the sensor if needed.
3. Replace the sensor.
The system will continue to operate using constant predefined values.
In addition, the display will alternate between “LO” and -11°F/-24°C
for low temperature readings, and between “HI” and 55°F/13°C for
high temperature readings.
Communication
error with snow
sensors
Error 1 – Communication error with one (or more) snow sensors
“SensErr 1” Will appear on display.
If the system is configured to work with more than 1 snow sensor, the faulty
snow sensor number will appear on display: P01, P02, P03 or P04.
The system will use readings from snow sensor 1 instead of the missing
readings from the faulty snow sensor.