Installation
Rev 1.2
Mellanox Technologies
31
Figure 25: Installing the Cage Nuts
While your installation partner is supporting the system’s weight, perform steps 3, 4 and 5:
Step 3.
On the rear side of the cabinet, install the two blades (B) in the selected rack unit, using four
M6 screws (C). Do not tighten the screws yet. See
Figure 26: Attaching the Rails to the Rack
Step 4.
Slide the two blades into the left and right rails, and adjust them to fit your rack's depth. Use
four M6 screws (D) to fix the blades into the rack. Do not tighten the screws yet. See
.
Figure 27: Sliding the Blades in the Rails
Step 5.
Secure the system in the rack by tightening the 8 screws inserted in Step 3 and Step 4 with a
torque of 4.5±0.5 Nm.