background image

Assembly for Mounted Receptacles 

(or Inlets)

In applications where DXN receptacles (or inlets) are 

mounted to wall boxes, panels or other equipment,  

optimal operation is achieved when the 

device is installed with the pawl/latch at the top. 

 

NOTICE:

 If the device is mounted to a wall box, make 

sure that appropriate hole plugs are securely tightened 

in any unused connection holes.

Insert the cable or wires through the wall box and 

cut 

to allow adequate length, strip the cable sheath, 

as desired, strip the individual wires to the lengths 

indicated in Table 3, and twist the strands of each  

conductor together.  Back out the terminal screws on 

the receptacle (or inlet) far enough (but not completely)  

to allow the conductors to pass, insert the conductors 

fully into their respective terminals and tighten the  

terminal screws to the torque indicated in Table 4, with 

a hand screwdriver.   

Assemble the receptacle (or inlet) and the color-coded 

gasket to the box with appropriate hardware.  

NOTICE:

 

Over-tightening the screws may cause cracking 

 

in polymeric components.  Assemble the mating plug 

(or receptacle) to the cord end as indicated in the 

assembly instructions above for in-line connections, 

except there will be no finger drawplate or associated 

black gasket.

In cases where custom mounting is being performed 

to an appropriate hazardous duty box or panel, the 

clearance and mounting holes should be drilled as 

indicated in the following diagram.

Hole Pattern for Custom Mounting

NOTICE:

 In order to maintain IP66/IP67 protection 

in custom installations, watertight seals must be used 

under the heads of the four mounting bolts and they 

must be retained by a lock washer and nut on the inside 

of the box or panel.  Alternatively, four blind holes can 

be drilled and threaded to accommodate #8-32 x 5/8" 

mounting screws. The hole depth must be sufficient to 

achieve adequate gasket compression.

 OPERATION

To ensure safe and reliable operation, 

MELTRIC plugs and receptacles must be used 

in accordance with their assigned ratings.

They can only be used in conjunction with mating 

receptacles or plugs manufactured by MELTRIC or 

another licensed producer of products bearing the 

 

 

technology trademark.

MELTRIC plugs & receptacles are designed with 

different keying arrangements, so that only plugs 

and receptacles with compatible contact configura-

tions and electrical ratings will mate with each other.   

Connection

To connect a plug and receptacle, first depress the 

pawl to open the lid on the receptacle, then orient 

the plug  1.  so that the red arrow on the outside of 

the casing lines up with the red arrow just to the left 

of the latch on the receptacle casing. Push the plug 

partially into the receptacle until it hits a stop, then 

rotate the plug in the clockwise direction until it hits 

another stop after about 30° of rotation. At this point, 

the circuit is still open.  Push the plug straight into 

the receptacle  2.  until it becomes securely latched in 

place. The connection is now made. For in-line connectors,  

squeeze the drawplates on both sides of the device 

together until the plug latches in place.  

NOTICE:

  When making a connection, ensure that 

the plug latch is secured behind the catch on the blue 

pawl. A properly connected plug cannot be pulled out 

of the receptacle.

Disconnection

To break the connection, simply depress the pawl 

as shown in figure  3. This will break the circuit and 

eject the plug straight out to the rest, or off, position. 

The plug contacts are de-energized at this point. To 

remove the plug, rotate it counterclockwise (CCW) 

(about 30°) until it releases from the receptacle as 

shown in figure  4. Close and latch the lid on the 

receptacle.

Achieving Watertightness Ratings

DXN’s have an IP66/IP67 rating for protection against 

ingress of water, dust and other matter. IP66 provides 

total protection against dust and water jets. IP67 adds 

protection for temporary immersion in shallow water.

These ratings apply when the plug and receptacle 

are mated. They also apply to the receptacle alone, 

provided that its lid is latched in the closed position. 

Optional plug caps are available for providing IP66/

IP67 protection on unmated plugs.

NOTICE:

 MELTRIC threaded handles come with 

tapered style threads.The use of fitting seal tape is 

recommended to maintain watertightness of all NPT 

fittings and joints.

Lockout Provisions

 

All DXN plugs are provided with lockout provisions. To 

lockout the plug, insert the locking device through the 

hole provided in the casing. This will prevent the plug 

from being able to be inserted into a receptacle.

Receptacles can be purchased with optional lockout 

provisions. MELTRIC’s Locking Pin must be used to 

lockout the receptacle. Close and latch the lid. Slide 

MELTRIC’s Locking Pin through the hole provided in 

the latch and place a padlock or other locking device 

through one of the holes on the locking pin. This will 

prevent the lid from being opened.

NOTICE:

 Attaching the receptacle locking device with 

the lid open will not prevent the insertion of a plug. 

Lockout is only accomplished when the lid is locked 

closed.

 MAINTENANCE

Before inspecting, repairing, 

or maintaining MELTRIC 

products, disconnect electrical power to the receptacle to 

eliminate the risk of electrical shock. Any replacement of 

DXN components must be performed under the control of 

the manufacturer: MELTRIC Corporation. 
MELTRIC products require little on-going maintenance.

However, it is a good practice to periodically perform 

the following general inspections:

 

• Check the mounting screws for tightness.

  •  Verify that the weight of the cable is supported 

by the strain relief mechanism and not by the  

terminal connections.

  •  Check the IP gaskets for wear and resiliency.

Replace as required.

 

•  Verify the electrical continuity of the ground circuit.

  •  

Check the contact surfaces for cleanliness 

 

and pitting.  

Deposits of dust or similar foreign materials can be 

rubbed off the male contacts with a clean cloth. Sprays 

should not be used, as they tend to collect dirt. If 

any significant pitting of the contacts or other serious  

damage is observed, the device should be replaced. 

Risk of electrostatic discharge: use a cloth slightly 

soaked in soapy water for cleaning

  MANUFACTURER’S RESPONSIBILITY

MELTRIC’s responsibility is strictly limited to the repair 

or replacement of any product that does not conform 

to the warranty specified in the purchase contract. 

MELTRIC shall not be liable for any penalties or 

consequential damages associated with the loss of 

production, work, profit, or any other kind of financial loss 

incurred by the customer.

MELTRIC Corporation shall not be held liable when 

its products are used in conjunction with products not 

bearing the 

 

technology trademark.  The use of 

MELTRIC products in conjunction with mating devices  

that  are  not marked  with  the 

 

 

technology  

trademark shall void all warranties on the product.

MELTRIC Corporation is an ISO 9001 certified company.   

Its products are designed, manufactured and rated in 

accordance with applicable UL, CSA and IEC standards.  

MELTRIC designs and manufactures its products in 

accordance with Marechal keying standards established 

to ensure intermatablility with similarly rated products 

manufactured by Marechal Electric Group.

DXN20: 1.656" 

           (

42mm

)

DXN30: 1.890" 

           (

48mm

)

DXN60: 2.171" 

           (

55.2mm

)

DXN20: 2.00" 

          (

51mm

)

DXN30: 2.25" 

          (

56mm

)

DXN60: 2.72" 

          (

69mm

)

DXN20: 1.656" (

42 mm

)

DXN30: 1.890" (

48 mm

)

DXN60: 2.171" (

55.2 mm

)

4 x Ø.196 

(

#9 or 5mm

)

INSDXN N

3

4

 GENERAL

MELTRIC’s DXN Series plugs & receptacles are 

designed and rated for use in hazardous environments 

where explosive gases or dusts may be present.  

The DXN receptacle has a dead front, which isolates 

the supply contacts and prevents user exposure to live 

parts. The receptacle’s safety shutter blocks access to 

the contacts and can only be opened by DXN plugs 

with compatible ratings and contact configurations.  

There are inherent dangers 

associated with electrical 

products. Failure to follow safety precautions can result in 

serious injury or death. These instructions must be  

followed to ensure the safe and proper installation, 

operation and maintenance of the MELTRIC devices. 

Before installation, disconnect all sources of power to 

the circuit to eliminate the risk of electrical shock.

  RATINGS & CERTIFICATIONS

To ensure the safe use of this product, the 

installer must verify that the product is properly 

rated for the application.

The amperage and voltage ratings are indicated on 

the device labels.  Some DXN devices are provided 

with optional auxiliary contacts that make after and 

break before the phase contacts. The ratings for 

 

auxiliary contacts are shown in Table 1.

Hazardous Duty Ratings

DXN plugs & receptacles have both ATEX and CSA 

ratings for use in hazardous environments.

ATEX – Class 1 Zone 1 AEx ed IIC T6

This rating certifies the product for use in surface 

(non-underground) applications where a high level 

of protection is required and where the presence of 

an explosive atmosphere of any type of gas or dust 

is likely to occur. The associated maximum surface  

temperature of the product is 85°C (185°F), at an 

ambient temperature of 40°C (104°F).

CSA –  

Class 1 Division 2 Group A, B, C, D 

 

Class 2 Division 2 Group E, F, G

This rating certifies the product for use in applications 

where flammable gases, such as acetylene, hydrogen, 

ethylene or propane, or dusts, such as magnesium, 

coal or grain, may be present under abnormal conditions.

 INSTALLATION

DXN’s must be used in conjunction with other 

appropriately rated hazardous duty products 

and must be installed by qualified electricians in  

accordance with all applicable local and national 

 

electrical codes.
Before starting, ensure that the power is off and verify  

that the conductors meet the requirements of the 

National Electric Code and are within the capacities of 

the DXN terminals noted in Table 2.

1

   Capacity is based on certification testing. Wire size  

should be determined in accordance with the electrical code.

2

  Auxiliary contacts are optional

General Notes & Precautions

1.   Self-tapping screws are provided for use with 

some polymeric accessories. High torque may  

be required to drive them in and fully seat 

the gasket/s. Once they are  seated, care 

should be taken in order to avoid over-tight-

ening them against the poly material. 

 

Poly Box with 70° Poly Angle accessory: 

 

captive screws must be tightened to a torque of 

1.2Nm (10.62 in-lbs)

   Metal Box with 70° Poly Angle accessory: 

 

   captive screws must be tightened to a torque  

    of 2.0Nm (17.7 in-lbs)

 

2. 

   

Wire strip lengths are indicated in Table 3.  

Strip lengths for cable sheathing will depend 

on the specific application. When used with 

handles, the cable sheathing should extend 

into the handle to ensure secure cord gripping. 

 

 

 

 

 

 

3.    Wiring terminals are spring assisted to prevent 

loosening due to wire strand settlement, vibration 

& thermal cycling. They should not be over-tightened. 

Appropriate tools and tightening torques are indicated 

in Table 4. 

NOTICE:

 Do not back terminal screws 

completely out.

Assembly for In-line Plugs/Connectors

Do not overtighten terminal or self-tapping 

screws. Tighten screws to the proper torque to 

ensure a secure connection.

Flexible cord connected devices must be equipped with 

a flexible cord listed for extra hard usage and terminated  

with listed fittings in accordance with all applicable 

local and national electrical codes. See table 6.

DXN devices are rated to make and withstand short 

circuit currents with appropriate fusing as indicated 

in Table 5.

When DXN’s are used as in-line connectors,

 

finger 

drawplates should be installed on both the receptacle 

and plug in order to more easily provide the leverage 

required to properly connect the devices.

 

Loosely re-assemble the compression nut, bushing and 

strain relief to the threaded adapter on the end of the 

handle and insert the cable through it, the thin black 

drawplate gasket and finger drawplate (if applicable), 

and the color-coded gasket.  Being mindful that the 

strain relief must clamp on the cable sheath, strip the 

cable sheath as required to provide a workable wire 

length. Then strip the individual wires to the lengths 

indicated in Table 3, and twist the strands of each 

conductor together. 

NOTICE:

 Back out the terminal screws on the receptacle 

 (or inlet) only far enough to allow the conductors to 

pass, insert the conductors fully into their respective 

terminals and tighten the terminal screws with a hand 

screwdriver to the torque indicated in Table 4. 

Verify that the cable jacket will extend beyond the 

strain relief and into the handle.  Assemble the 

receptacle (or inlet), the color-coded gasket, the 

finger drawplate, and the thin black finger drawplate 

gasket to the handle with the four self-tapping screws  

provided. 

NOTICE

: Over-tightening the screws may 

cause cracking in polymeric components. Adjust the 

cable location so that it will not be under tension inside 

the handle and tighten the compression nut to secure 

the cable.

Short Circuit MELTRIC’s DXN Series Plugs & 

Receptacles have short circuits make (close) and 

withstand ratings up to 25kA when used with the  

fusing shown in Table 5.

Compression

Nut

Handle

Strain

Relief

Color-Coded

Gasket

Receptacle

(or Inlet)

Bushing

Threaded

Adapter

Finger Drawplate Gasket

DXN20 Remove Adhesive Liner

Finger Drawplate

DXN20 

7.1 in-lbs 

1/8" precision tip

DXN30 

(Main Contacts)

  10.6 in-lbs 

3/16" precision tip

DXN30 

(Aux. Contacts)

  7.1 in-lbs 

1/8" precision tip

DXN60 

(Main Contacts)

  17.7 in-lbs 

3/16" precision tip

DXN60 

(Aux. Contacts)

  7.1 in-lbs 

1/8" precision tip

Table 4 - Recommended Tightening Torques

 Terminal 

Torque  Flat Screwdriver

  

Inches 

mm

 DXN20 - Main 

0.50/0.50 12/12

 DXN30 - Main 

0.79/0.83 20/21

 DXN30 - Aux. 

0.67/0.67 17/17

 DXN60 - Main 

0.79/0.83 20/21

 DXN60 - Aux 

0.67/0.83 17/21

Table 3 - Wire Strip Length - A (receptacle/inlet)

 

 

Max Min 

Max 

 DXN20 

10 

16 

N/A 

 DXN30 

14 

10 

 DXN60 

10 

10 

Table 2 - Wiring Terminal Capacity

1

 - AWG

  

Main Contacts  

Aux. Contacts

2

 

Table 1 - Auxiliary Contact Ratings

        Device  120VAC  240VAC  480VAC  600VAC

 

DXN30,60  5A* 5A* 5A* 

5A* (550V max)

  Extra Hard 

0.812 0.312 

  Usage

Table 6 - Flexible Cord

 

 

Type

 

Max Nos of 

Flexible Cable Range 

  

 

  

Conductors 

Max Øin 

Min Øin

 

Device 

Rating Fuse 

Type*

 

DXN20 - 20A 

25 kA@600VAC 

RK1 

30A 

 DXN30 - 30A 

25 kA@600VAC 

RK1 

70A 

 DXN60 - 60A 

25 kA@600VAC 

RK1 

100A

Table 5 - Short Circuit Make & Withstand Ratings

*   DXN20, 30 Ratings are based on testing with Mersen  

Non-Time delay current limiting fuses 

DXN60 Ratings are based on testing with Little Fuse 

Non-Time delay current limiting fuses

* Note: Consult NEC for short circuit limits

INSDXN N

A COMPANY OF MARECHAL ELECTRIC

MELTRIC Corporation / 4765 W. Oakwood Park Drive Franklin, WI 53132

Tel. : 800 433 7642 / Fax : 414 433 2701 / e-mail : mail

@

MELTRIC.com 

A manufacturer of products using Marechal technology

MELTRIC

.com

©2019 MELTRIC Corporation.  All rights reserved.  

DX

CONSIGNES D’UTILISATION

DXN SERIES

ENGLISH OPERATING INSTRUCTIONS

  RENSEIGNEMENTS GÉNÉRAUX

Les fiches et prises de la série DXN de MELTRIC sont 

conçues et homologuées pour les environnements 

dangereux qui comprennent des poussières ou des 

gaz explosifs.  

La prise DXN est équipée d'un écran isolant qui 

couvre les contacts et empêche l'exposition aux 

pièces sous tension.  Le mécanisme d'obturation de 

la prise bloque l'accès aux contacts et ne peut être 

ouvert qu'en insérant une fiche DXN dont les calibres 

et la configuration sont compatibles.  

Il existe des dangers 

inhérents aux produits 

électriques. Le non-respect des règles de sécurité 

peut entraîner des blessures graves ou la mort. Les 

présentes instructions doivent être suivies pour 

assurer une installation, une utilisation et un entretien 

adéquats et sécuritaires. Avant l'installation, 

débranchez toute source d'alimentation du circuit afin 

d'éliminer les risques d'électrocution.

  CALIBRES ET HOMOLOGATIONS

Pour utiliser ce produit de façon sécuritaire, 

l'installateur doit s'assurer que le calibre 

convient à l'utilisation prévue.  

L'intensité et la tension nominales sont indiquées sur 

les étiquettes de l'appareil.  Certains appareils DXN 

sont équipés de contacts auxiliaires optionnels qui 

se connectent après les contacts de phase, mais qui 

se déconnectent avant ces derniers. Les calibres des 

contacts auxiliaires sont indiqués dans le tableau 1. 

Homologations pour environnements dangereux

Les fiches et prises DXN sont conformes à la 

réglementation ATEX et homologuées par la CSA 

pour les environnements dangereux.

ATEX – Classe 1, Zone 1, AEx ed IIC T6

Cette classification certifie que le produit convient aux 

utilisations au niveau du sol (non souterraines) qui 

exigent beaucoup de protection et où l'atmos-phère 

peut être explosive en raison de la présence d'un 

gaz ou de poussières.  La température max-imale à 

la surface de l'appareil est de 85 °C (185 °F), à une 

température ambiante de 40 °C (104 °F).

CSA –  Classe 1, Division 2, Groupe, A, B, C, D

 

Classe 2, Division 2, Groupe E, F, G

Cette classification certifie que le produit convient 

aux utilisations pour lesquelles, dans des conditions 

anormales, des gaz inflammables (comme l'acétylène, 

l'hydrogène ou le propane) ou des poussières 

inflammables (comme la poussière de magnésium 

ou de charbon ou la poussière céréalière) peuvent 

être présents.

 INSTALLATION

Les appareils DXN doivent être utilisés avec 

du matériel de calibre approprié et doivent être

installés par des électriciens qualifiés, dans le respect 

des normes locales et nationales sur l'électricité.

Avant de commencer, assurez-vous que l'alimentation 

est coupée, que les conducteurs sont conformesau 

National Electric Code

 et que leurs capacités 

correspondent aux valeurs indiquées dans le tableau 2 

pour les bornes DXN.

1

 Capacité indiquée pour des fils de type THHN.

2

 Les contacts auxiliaires sont optionnels.

Remarques et précautions générales

1.   Des vis autotaraudeuses sont fournies pour la 

pose de certains accessoires en polymère. Un 

torque élevé peut être requis pour les fixer 

complètement dans le joint d’étanchéité, mais 

prenez soin de ne pas trop les serrer sur le matériau.  

Les boîtes en polyester avec angle de 70° en 

polyester; les vis captives doivent être serrés 

avec un torque de 1.2Nm (10.62 pouce-livre). 

 

Les boîtes en métal avec angle de 70° en polyester; 

les vis captives doivent être serrés avec un torque de 

2.0Nm (17.7 pouce-livre)

2.   Les longueurs de fil dénudé sont indiquées au 

tableau. 3. La longueur de câble à dénuder 

dépend de l'utilisation prévue.  Pour fixer un câble 

à une poignée, assurez-vous que la gaine du 

câble dépasse à l'intérieur de la poignée pour que 

le cordon offre une bonne prise.

3.   

Les bornes de raccordement sont dotées de 

ressorts pour empêcher la formation d'un jeu 

causée par le déplacement des brins des câbles, 

les vibrations et les cycles thermiques. Elles 

ne doivent pas être trop serrées. Les outils et 

couples de serrage appropriés sont indiqués 

dans le tableau 4. 

ATTENTION: 

Ne dévissez pas 

complètement les vis des bornes.

Assemblage pour prises ou connecteurs en série

Ne serrez pas trop les vis des bornes et les 

vis autotaraudeuses. Serrez les vis au couple 

approprié pour assurer une bonne connexion.

Les produits à raccord avec cordon flexible doivent 

être utilisés avec un cordon flexible à usage intense et 

munie d’accessoires de raccord selon les lois et normes 

en vigueur localement et selon le code électrique. Voir 

tableau 6. 

Les produits de la série DXN sont fait pour supporter 

et maintenir un courant de court-circuit selon les 

spécifications du tableau 5 lorsque protégé par fusible. 

Pour l'utilisation d'un appareil DXN comme connecteur 

en série, il est préférable d'installer des plaques de 

levage sur la prise et sur la fiche afin de faciliter les 

branchements et débranchements.

Sans les serrer, remontez l'écrou de compression, 

l'embout et le serre-câble sur l'adaptateur fileté à 

l'extrémité de la poignée, puis faites passer le câble 

dans l'adaptateur, dans la plaque de levage et son 

mince joint d'étanchéité noir (si l'appareil en est 

équipé), et dans le joint d'étanchéité à code de 

couleur.  En vous assurant que le serre-câble retient 

bien la gaine du câble, dénudez le câble de sa gaine 

de manière à obtenir une longueur suffisante pour 

travailler. Dénudez ensuite chaque fil en respectant les 

longueurs indiquées dans le tableau, puis entortillez 

les brins de chaque conducteur.  

ATTENTION :

 Dévissez les vis des bornes de la 

prise juste assez pour pouvoir passer les conducteurs, 

enfoncez complètement les conducteurs dans leurs  

bornes respectives et serrez les vis des bornes à l'aide 

d'un tournevis, au couple de serrage indiqué dans le 

tableau 4.  

Assurez-vous que la gaine du câble dépasse 

le niveau du serre-câble et pénètre dans la 

poignée.  Installez la prise, le joint d'étanchéité à 

Tableau 4 – Couples de Serrage Recommandés

Borne

Couple

Tournevis Plat

DXN20

7,1 lb-po

pointe de 1/8 po

DXN30 (Contacts Princ.)

10,6 lb-po

pointe de 3/16 po

DXN30 (Contacts Aux.)

7,1 lb-po

pointe de 1/8 po

DXN60 (Contacts Princ.)

17,7 lb-po

pointe de 3/16 po

DXN60 (Contacts Aux.)

7,1 lb-po

pointe de 1/8 po

Écrou de

compression

Poignée

Serre-

câble

Joint à code

de couleur

Prise

Embout

Adaptateur

fileté

Joint d'étanchéité de la plaque de levage

DXN20 enlever l’auto-collant

Plaque de levage

WARNING

DANGER

CAUTION

NOTICE

WARNING

DANGER

CAUTION

NOTICE

WARNING

DANGER

CAUTION

NOTICE

Tableau 1 – Calibre des Contacts Auxiliaires

Appareil

120V 

c.a.

240V 

c.a.

480V 

c.a.

600V c.a.

DXN30, 60

5A*

5A*

5A*

5A* (550V max)

Tableau 2 – Capacité des bornes

1

 -- AWG

Contacts Princ.

Contacts

2

Max

Min

Max

DXN20

10

14

S.O.

DXN30

6

12

10

DXN60

4

10

10

Tableau 3 – Longueur à Dénuder -- A (prise)

Pouces

mm

DXN20 –   Princ.

0,50/0,50

12/12

DXN30

–   Princ.

0,79/0,83

20/21

DXN30

–   Aux.

0,67/0,67

17/17

DXN60

–   Princ.

0,79/0,83

20/21

DXN60

–   Aux.

0,67/0,83

17/21

  Usage 

0.812 0.312 

  Intense

Tableau 6 – Cordon flexible

 

   

Tipo

 

Nbre de 

 

Plage du câble 

  

 

   conducteur max 

Max Øpouce  Min Øpouce

 

Produit 

Calibre du fusible 

Type*

 

DXN20 - 20A 

25 kA@600VAC 

RK1 

30A 

 DXN30 - 30A 

25 kA@600VAC 

RK1 

70A 

 DXN60 - 60A 

25 kA@600VAC 

RK1 

100A

Tableau 5 – Niveau de courant de court-circuit 

supporté et maintenu

*   Les niveaux pour DXN20, 30 sont basés sur les essais 

fait avec des fusibles Mersen à action rapide limiteur 

de courant.

    Les niveaux pour DXN60 sont basés sur les essais fait 

avec des fusibles Littelfuse à action rapide limiteur de 

courant.

* Note: Consulter NEC pour les limites de court-circuit

INSDXN N

A COMPANY OF MARECHAL ELECTRIC

MELTRIC Corporation / 4765 W. Oakwood Park Drive Franklin, WI 53132

Tel. : 800 433 7642 / Fax : 414 433 2701 / e-mail : mail

@

MELTRIC.com 

A manufacturer of products using Marechal technology

MELTRIC

.com

©2019 MELTRIC Corporation.  All rights reserved.  

DX

CONSIGNES D’UTILISATION

SERIE DXN

FRANÇAIS CONSIGNES D’UTILISATION

Pawl

Latch

Receptacle

Plug/Inlet

1

2

INSDXN_N.indd   1

INSDXN_N.indd   1

12/20/19   1:09 PM

12/20/19   1:09 PM

Summary of Contents for DXN30

Page 1: ...isted fittings in accordance with all applicable local and national electrical codes See table 6 DXN devices are rated to make and withstand short circuit currents with appropriate fusing as indicated in Table 5 When DXN s are used as in line connectors finger drawplates should be installed on both the receptacle and plug in order to more easily provide the leverage required to properly connect th...

Page 2: ...isted fittings in accordance with all applicable local and national electrical codes See table 6 DXN devices are rated to make and withstand short circuit currents with appropriate fusing as indicated in Table 5 When DXN s are used as in line connectors finger drawplates should be installed on both the receptacle and plug in order to more easily provide the leverage required to properly connect th...

Page 3: ...otection contre la poussière et les jets d eau IP 67 fait référence à la protection en cas d immersion temporaire dans une eau peu profonde Cesprotectionssontactivesquandlaficheestbranchéedans la prise La prise seule offre les mêmes protections lorsque le couvercle est fermé et verrouillé Des couvercles optionnels pour fiches sont offerts pour assurer la protection des classificationsIP66etIP67lor...

Page 4: ...otection contre la poussière et les jets d eau IP 67 fait référence à la protection en cas d immersion temporaire dans une eau peu profonde Cesprotectionssontactivesquandlaficheestbranchéedans la prise La prise seule offre les mêmes protections lorsque le couvercle est fermé et verrouillé Des couvercles optionnels pour fiches sont offerts pour assurer la protection des classificationsIP66etIP67lor...

Page 5: ...isted fittings in accordance with all applicable local and national electrical codes See table 6 DXN devices are rated to make and withstand short circuit currents with appropriate fusing as indicated in Table 5 When DXN s are used as in line connectors finger drawplates should be installed on both the receptacle and plug in order to more easily provide the leverage required to properly connect th...

Page 6: ...otection contre la poussière et les jets d eau IP 67 fait référence à la protection en cas d immersion temporaire dans une eau peu profonde Cesprotectionssontactivesquandlaficheestbranchéedans la prise La prise seule offre les mêmes protections lorsque le couvercle est fermé et verrouillé Des couvercles optionnels pour fiches sont offerts pour assurer la protection des classificationsIP66etIP67lor...

Reviews: