14
Chapter 3 • Installation
User Manual FSK700-2 / FSK700-2SX
3
Installation
3.1
General
Installation and commissioning of the Series FSK700 Fire Brigade Key Safe is to be performed by
a specialist company trained and authorised by MEP-Gefahrenmeldetechnik GmbH or their local
representative. All relevant standards and regulations must thereby be observed (see page 11 and
onwards in chapter 1.11: "Standards, Guidelines, CE marking").
1)
Optional Weather Protection Hood WSD-FSK
Fig. 4:
Dimensions of the Series FSK700 Key Safe, starting from production number 08/06806
The Key Safe is to be inserted in the Flush Mounting Frame EZ700-2, MEP Article No. 265751,
which must be tightly grounded in the wall. Should the wall not be sufficiently solid (see page 14
and onwards in chapter 3.2: "Installation site"), the Flush Mounting Frame with Drill Protection
EZBS700-2, MEP Article No. 265818 must be utilised instead.
Instructions for installation of the Key Safe in the Key Safe Column SDS700-2 are provided in
the manual "Key Safe Column SDS700-2" by MEP-Gefahrenmeldetechnik GmbH.
Controlling and monitoring of the Key Safe must be performed using a VdS-certified controlling
and monitoring device (such as Key Safe Controlling and Monitoring Device AD900-1, MEP Art-
icle No. 265900).
Instructions for installation of the controlling and monitoring device are provided in the manual
of the respectively used device.
3.2
Installation site
The Key Safe is to be installed in accordance with the local fire brigade, preferably in a weather-
proof location (i.e., in an alcove, passageway, or under a canopy), flush mounted in the wall. The
bottom edge of the Key Safe should be located about 1.2m (at least 0.8m) above the floor.
The wall in which the Key Safe (i.e., Flush Mounting Frame EZ700-2) is to be installed in must be
made from stone work according to DIN 1053, bricks according to DIN 105, lime-sand bricks
according to DIN 106, or from reinforced concrete (minimum B 25 according to DIN 1045). The
wall must be at least 80mm thicker than the installation depth of the Key Safe.
Should no adequately solid wall suitable for installation of the Key Safe be available (e.g., only
walls with thermal insulation), the Flush Mounting Frame with Drill Protection EZBS700-2 must
be utilised to improve security and protect against sabotage.
HB_FSK700_1020_9161690_Englisch_D.odt / 1022 D / AN9161690
ZN62163/38/14
14