34
Chapter 6 • Inspection, maintenance, service
User Manual FSK700-2 / FSK700-2SX
Terminals on
State
Nominal value
AD900-1 FSK700
25 / 2
11 / 2 Voltage with master key inserted
U
B
=12V: > 8VDC
U
B
=24V: > 16VDC
Voltage with master key removed
<0.5VDC
Resistance with master key inserted
>10MΩ
Resistance with master key removed
<10Ω
Table 3:
Overview of the various states and corresponding nominal values
U
B
… Operating voltage of the Key Safe Controlling and Monitoring Device
U
H
… Heater voltage
HB_FSK700_1020_9161690_Englisch_D.odt / 1022 D / AN9161690
ZN62163/38/34