Zero Suppression: Select
0n
or
0FF
. Factory default is
0n
.
0FF
The input range will start at 0 (zero) Input.
0n
The input range will start at 4.00 mA or 2.00 V.
1nP
Input Type: Select one of the following. Refer to the Input wiring section for
the proper wiring. Factory Default is
Curr
.
Curr
DC Current Input 0.0 to 20.0 or 4.0 to 20.0 mA.
UoLt
DC Voltage Input 0.0 to 10.0 or 2.0 to 10.0 volts.
- - - -
Reserved
P0t
Pump Over Temperature: Select
AUt0
or
rES
. When pump temperature sensor
indicates that there is an over temperature condition the pump will be held out of
service and the corresponding pump over temperature lamp is lit on the controller.
If using the MPC with two pumps and lead/lag on then the remaining pump
becomes the lead pump. If lead/lag is turned off then the remaining pump
becomes controlled by Set Point 1. See page 12.
AUt0
The pump will be automatically placed back into service and the
lamp turned off when the over temperature condition has ceased.
rES
The pump will remain out of service and the lamp lit until the
corresponding manual reset
P10t
or
P20t
is reset in the
Secondary menu. The pump cannot be brought back into service until
the over temperature condition has ceased.
PSF
Pump Seal Failure: Select
AUt0
or
rES
. See page 11.
AUt0
When pump moisture sensor indicates that there is a seal failure condition
the corresponding pump seal failure lamp is lit on the controller. The pump
will remain in service with only the lamp indication of failure. The lamp will
automatically turn off when failure condition ceases.
rES
When pump moisture sensor indicates that there is a seal failure
condition the corresponding pump seal failure lamp is lit on the
controller. If the MPC is being used with two pumps and the lead/lag
feature turned on then the failed pump will automatically become the lag
pump, the remaining pump the lead pump, and the alternation
discontinued. The seal failure action is reset manually with the values of
P1SF
and
P2SF
in the Secondary menu. The control will only reset if the
pump moisture sensor is no longer in a failed condition.
tESt
System Test: Select
0n
or
0FF
. When
0n
is selected the ˝System Test˝ key on
the
front panel will be activated. By depressing this key for 3 seconds the controller
will simulate an input from
SCAL
to
SCAH
and back to
SCAL
over a period of 32
seconds. This test will run continuously until the SYSTEM TEST key is pressed
again. When the controller is in System Test Mode the lamp above the System
Test Key will be ON.