Fig. 12.
Example mcr EXi-F air supply unit in wall-mounted version (installation outdoors)
(1 - fan in a box housing, 2 - flexible connection, 3 - damper with actuator, 4 - air intake, 5 - vibro-isolating pad or
shock absorbers, 6 - smoke detector, 7 - supporting structure, 8 - protective mesh)
Fig. 13.
Example horizontal installation of mcr EXi-F air supply unit
(1 - fan in box housing, 2 – ventilation duct, 3 – damper,
4 – duct smoke detector, 5 – flexible connector, 6 – fan inlet protection, 7 – junction box, 9 – noise suppresor)
4.2.
Differential pressure transmitter
____________________________________________
4.2.1.
mcr ICS digital differential pressure transmitter
______________________________
The device measures differential pressure in a protected area at increase pressure (staircases,
lift shafts, protected lobbies, exit access corridors). The device should be connected to two pressure
line. The measurement results are transmitted in real time via a digital interface to the regulator
controlling fan operation (via an inverter).