EXi-F
positive pressure smoke control system
„MERCOR” S.A. –
Specifications are subject to change without notice. Version DTR_EXIF_EN_20220516
Page
22
/ 28
Fig. 19.
Example manual control panel view.
5.
WIRING SYSTEM
_________________________________________________
5
.1.
mcr Omega control supply unit
The control unit is used for controlling and monitoring mcr EXi-F pressure differential system
components.
Main automatics system tasks:
power supply, control and monitoring of the air supply fans for positive pressure via signals from
the fire alarm control panel (FACP),
power supply, control and monitoring of the air control and shut-off dampers,
power supply and operation of the duct smoke detector,
power supply, control and monitoring of dampers used in differential pressure system.
The control unit is supplied with 3 x 400 V. The control supply unit is powered by an incoming
panel for fire protection equipment, which is not disconnected with a fire switch or is equipped with an
automatic reserve power switch (ARPS) in buildings, where no incoming panel for fire protection
equipment is available in the main switchboard.
Detailed wiring diagrams, dimensions, number and type of components used result from
the design requirements for a specific building and are included as annexes to this Operation
and Maintenance Manual.
power supply
lock - blinking
failure – on
fire alarm
air supply unit
operation
CONTROL
0 - Auto
I - Test
II - Stop
mcr EXi-F MANUAL CONTROL PANEL