Fig. 22.
Pressure line installation guide.
If the pressure measurement points are at a large distance from the pressure transmitter,
additional set of pressure lines (5 m long and 8 mm diameter) can be used (maximum total pressure
line length should not exceed 12 m).
Additional set of pressure lines include 4 fittings (2 elbows and 2 straight connectors).
Fig. 23.
Additional pressure line set with accessories.
Pressure system outside the building should be made with silicone pressure lines (resistant to
low temperature). Protect the ends of the hydraulic lines against accidental blocking. Use back boxes
with pre-drilled holes in the cover.
5.4. Damper actuators
mcr EXI-F air supply units are also available with multi-blade dampers with Belimo
BLF/BF/BFL/BFN, BLE/BE, NMQ/LMQ/SMQ, NF/SF or Mercor MF/MLF