Number of modules connected to the panels:
1. Maximum number of modules:
mcr PROSMOKE FS
modules in the mcr 9705 control unit
– 12 modules
mcr PROSMOKE FS
modules in the mcr 0204 control unit
– 8 modules.
If a group of curtains with a higher number of modules is necessary, they should be
divided into sections or an extension module should be used to power them.
2. The time of keeping the curtain rolled up by the control unit if there is no primary
power supply:
mcr 0204
– up to 12 hours for 1 pc. (2 pcs. – 6 hours; 3 pcs. – 4 hours, etc.).
mcr 0204
– up to 20 hours for 1 pc. (2 pcs. – 10 hours; 3 pcs. – 6.5 hours, etc.).
3. The control unit and each curtain module requires a 230 V power supply.
4. The maximum power of a 230 V motor in a single module is 270 W.
Limit switch adjustment:
The
mcr PROSMOKE FS
only has the upper position limit switch.
The lower position limit switch is blanked off (photo 1)
– the curtain drops until it is
fully rolled out.
1. The limit switch is marked with up/down arrows which correspond to the direction
of the motor rotation. +/- symbols indicate the change in range.
2. The switch trigger point can be moved as indicated by the arrow by rotating the
adjustment screw t or in the opposite direction by rotating the adjustment
screw towards -.
3. One turn of the adjustment screw changes the rotation of the motor shaft by
approx. 10
(which translates into approx. 1 cm of the curtain fabric).
4. To set the limit switch precisely and to check if it functions correctly, trigger the
switch, having first changed its setting by r
educing the value by at least ¼ turn.
Fig. 6. Curtain limit switch adjustment