mcr WIP PRO
multi-blade fire damper
„
MERCOR” S.A. –
All rights reserved to modifications without prior notice
6/25
Fire dapmer mcr WIP PRO with spring gear.
Mechanizm
A
C
D
RST/KW1/S,RST/KW1/24P
298
120
75
5. DEVICE IDENTIFICATION _________________________________________
mcr WIP PRO/...
B x H
/1
/2
/3
6. INSTALLATION
____________________________________________________________
CAUTION
During the installation of the damper and finishing works with it, there is a need to consider
possibility of future access to the device and possibility of disassembly the control-release
mechanism in order to perform maintenance or technical review.
The mcr WIP PRO dampers can be installed in the following building partitions (i.e. walls or ceilings):
masonry concrete walls min. 120 [mm] thick in variants /S, /T, /V, /V-M
masonry walls made of bricks or blocks min. 120 [mm] thick in variants /S, /T, /V, /V-M
panel walls min. 125 [mm] thick in variants /S, /T, /V, /V-M
floor slabs min. 150 [mm] thick in variant /S
*Dampers mounted in the floor slabs, may have a maximum dimension BxH: 1000x1000mm
Additionally, the fire dampers can be installed:
outside of walls
in dampers sets (multiple damper sets)
Optional fittings
Material
Trigger control gear
Width x height / diameter (nominal)
Damper type