mcr WIP type multi-blade fire dampers 

 

 

 

“MERCOR” S.A. – 

the Company reserves the right to make modifications and changes. 

 

14/15 

 

installing a fire damper, place it in such a way so that it is supported on its side panels or body edges. Fire dampers 
should  be  stored  in  closed  interior  spaces  which  ensure  protection  against  the  weather.  When  fire  dampers  are 
stored on the floor, they should be placed on protective supports in order to protect them against damage. 

 

8.

  MAINTENANCE AND SERVICE (REPAIRS)  

 

Products manufactured by „MERCOR” S.A. should undergo periodic technical inspections and maintenance at least 
every  12  months  throughout  their  service  life,  i.e.  in  the  warranty  period  and  later.  Inspections  and  maintenance 
should be carried out by the manufacturer or by companies authorised to service „MERCOR” S.A.’s products. 
The obligation  to  conduct  regular  inspections  of  fire equipment is  stipulated  in  §  3  section 3  of  the Regulation  of 
Minister of Internal Affairs and Administration dated 7 June 2010 on the fire protection of buildings, other structures 
and areas (Dz. U. [Journal of Laws] 2010 No. 109, item 719). 
The recommended activities to be carried out between the inspections are as follows: 

 check the condition of electrical connections, paying particular attention to mechanical damage; 

 

Inspections of the condition of the supply voltage for the devices, which allowed the following tolerances: 

 

24V±10% for electric actuators 

 

24V±2% for electromagnetic release mechanism 

 

230V ±10% for electric actuators 

 

230V±2% for electromagnetic release mechanism 

 check the condition of the fire damper’s body, paying particular attention to mechanical damage; 

 check for causes that could possibly affect the correct operation of the fire damper. 

To  enable  full  service  inspections  as  well  as  servicing,  including  servicing  under  the  warranty,  such  as  visual 
inspections  and  repairs,  the  user  has  to  ensure  physical  access  to  the  product,  e.g.  by  removing  thermal 
insulation/suspended ceilings and disassembling other systems if they prevent free access to the product, etc. 
In the case of fire dampers installed in ducts, it is recommended to make a service duct such as the mcr KRW type, 
for instance. 
Should fire dampers be installed on a roof, access to the roof should be ensured by providing a ladder or lift. 

 

For matters relating to technical inspections, maintenance and service of our products, please contact the Service 
Department of „Mercor” S.A. at serwis@mercor.com.pl, phone 058/341 42 45 (extension number 170), fax 058/341 
39 85, 8 am–4 pm (Mon–Fri). 

 

9.  WARRANTY TERMS AND CONDITIONS 

 

1. 

„MERCOR”  S.A.  gives  a  12-month  quality  warranty  for  the  products  and,  unless  an  agreement  provides 
otherwise, the warranty period begins on the day of purchase. 

2. 

Should physical defects be identified in the warranty period, „MERCOR” S.A. undertakes to rectify them no 
later than 21 days from the receipt of a written complaint and a proof of purchase or agreement, subject to 
item 6. 

3. 

„MERCOR”  S.A.  reserves  the  right  to  extend  the  repair  time  in  the  case  of  complex  repairs  or  those 
necessitating a purchase of non-standard components or spare parts. 

4. 

Liability  in respect of warranty shall only cover defects arising from causes originating  in the sold  products 
themselves. 

5. 

In  the  event  of  defects  due  to  improper  operation  of  products  or  other  reasons  indicated  in  item  6,  the 
purchaser/warranty holder shall bear the cost of removing such defects. 

6. 

The warranty shall not cover any of the following: 

 

Damage and failures of products caused by  improper use, user’s tampering with product and lack of 
periodic technical inspections/maintenance described  in section “SERVICE AND MAINTENANCE” of 
this document. 

 

Damage  of  products  due  to  other  causes  than  those  attributable  to  „MERCOR”  S.A.,  in  particular 
fortuitous events such as torrential rain, flood, hurricane, flooding, strike of lightning, mains overvoltage, 
explosion, hail, aircraft crash, fire, avalanche, landslide and secondary damage resulting from the above 
causes.  Torrential  rain  shall  mean  rain  with  rainfall  intensity  of  at  least  4,  as  determined  by  IMiGW 
[Institute of Meteorology and Water Management]. If rainfall intensity cannot be determined, the actual 
conditions and extent of damage at the place of damage, proving the event of torrential rain, shall be 
taken  into  consideration.  Hurricane  shall  mean  wind  speed  of  at  least  17.5  m/s  (damage  shall  be 
deemed to be caused by a hurricane if hurricane is proven to have occurred in the proximity). 

 

Damage caused as a result of failing to report immediately a discovered defect 

 

Deterioration of the quality of coating caused by natural ageing processes. 

 

Defects caused by the use of abrasive or corrosive cleaning agents. 

 

Damage  caused  by  aggressive  external  agents,  especially  chemical  and  biological,  or  such  agents 
whose origin is related to the production processes and activities carried out in a facility or its immediate 
proximity where the products have been installed. 

 

Parts  subject  to  normal  wear  and  tear  during  operation  (e.g.  seals)  unless  they  are  found  to  have 
manufacturing defects. 

 

Defects caused by improper transport, unloading or storage of the product. 

Summary of Contents for mcr WIP Series

Page 1: ...Ul Grzegorza z Sanoka 2 80 408 Gdańsk Phone 0 58 341 42 45 OPERATION AND MAINTENANCE MANUAL OMM mcr WIP fire damper Rev WIP 18 11 14 15 FIRE VENTILATION SYSTEMS DEPARTMENT ...

Page 2: ...NG PRINCIPLE OF THE FIRE DAMPER 4 5 MANUFACTURER S DESIGNATION OF THE FIRE DAMPER 5 6 INSTALLATION OF THE FIRE DAMPER 6 6 1 PRE INSTALLATION INSPECTION 6 6 2 INSTALLATION OPENING 6 6 3 BUILDING IN THE FIRE DAMPER 7 6 4 ELECTRICAL CONNECTIONS 12 7 TRANSPORT AND STORAGE CONDITIONS 16 8 MAINTENANCE AND SERVICE REPAIRS 16 9 WARRANTY TERMS AND CONDITIONS 16 Markings used in the OMM Option available Opt...

Page 3: ...ce of fire damper installation Manufacturing versions The mcr WIP type fire dampers may be manufactured as rectangular fire dampers rectangular fire dampers with circular connections round fire dampers Series of types of dimensions The mcr WIP type fire dampers are manufactured in the following dimensions width from 120 to 1 000 mm height from 160 to 1 000 mm rectangular fire dampers width 140 mm ...

Page 4: ...thout a return spring after applying voltage to the appropriate contact After widespread of the fire the damper closes after activation by the building fire protection system by applying voltage to the appropriate contact of the damper If dampers remain open during normal operation safety position air transfer closing them takes places automatically by actuation of the thermoelectric release manua...

Page 5: ...le conducting finishing work you should allow for the possibility of later access to the fire damper and removal of the release and control mechanism in order to carry out possible service work and technical inspections The mcr WIP fire dampers may be installed in the following space dividing elements walls or structural floors masonry concrete walls with a thickness of 120 mm brickwork walls or c...

Page 6: ...ially in a space dividing element a wall or structural floor that divides separate fire compartments i e in a previously prepared opening Next level and secure the fire damper so that it does not move For fire dampers with dimensions greater than 700 x 700 a strut should be used Once the above have been completed start manually the fire damper s partition blades assembly checking if it rotates cor...

Page 7: ...ectly When installing the mcr WIP type fire dampers ensure in particular that the thermal release fusible component is not damaged It should not be exposed to high temperature fire welders soldering irons which causes its actuation it is a component that has been designed to be used once only and will not be replaced under warranty Similarly the intumescent seals installed in the housing of the fi...

Page 8: ...nstallation of the protective grid for the mcr WIP type fire damper Protective grid thickness G shown in the figures should have 30 50mm depending on the thickness of the wall in 1 Grid blades 2 Internal frame 3 External frame 4 4 8 diameter rivet Modular protective grid for the mcr WIP type fire damper A modular protective grid may be supplied by the manufacturer of the fire damper or made by the...

Page 9: ...ations of the mcr WIP dampers modules can be made consisting of two or more dampers while maintaining the minimum distances between the dampers according to the drawing above 6 4 ELECTRICAL CONNECTIONS Once a fire damper has been correctly installed it is necessary to connect it to the electrical wiring system using the wiring system s cables if the fire damper is equipped with controls or other c...

Page 10: ...rating IP 54 IP 54 IP 54 IP 54 auxiliary switch activation point degrees 2 x PDT 3 0 5 A AC 250V 2 x PDT 3 0 5 A AC 250V 2 x SPDT 3 0 5 A 250 V 2 x SPDT 3 0 5 A 250 V 5 80 5 80 5 80 5 80 Torque motor spring 4 Nm 3 Nm 4 Nm 3 Nm 9 Nm 7 Nm 9 Nm 7 Nm Wire connection motor length 0 9 m auxiliary switch 2 x 0 75 mm2 6 x 0 75 mm2 2 x 0 75 mm2 6 x 0 75 mm2 2 x 0 75 mm2 6 x 0 75 mm2 2 x 0 75 mm2 6 x 0 75 m...

Page 11: ... T actuators Wiring diagram for BFL24 T BFL230 T BFN24 T and BFN230 T actuators Notice 24 V connection through a safety transformer Several actuators may be connected in parallel Power consumption should be monitored Notice 24 V connection through a safety transformer Several actuators may be connected in parallel Power consumption should be monitored ...

Page 12: ...d by the warranty conditions Technical data actuators EXBF 24 EXBF 230 Power supply 24 V AC 20 50 60 Hz 24 VDC 10 20 230 V AC 14 50 60 Hz Power demand when putting the spring under tension when in standby 7 W 2 W 8 W 3 W Apparent power 10 VA 12 5 VA IP rating IP 66 IP 66 Auxiliary switch activation point 2 x SPDT 6 A 3 max 250 V AC 5 80 2 x SPDT 6 A 3 max 250 V AC 5 80 Torque motor spring 18 Nm 12...

Page 13: ... NC type normally closed Wire no 7 8 NC type normally closed Warning Location of limit switches of the mechanism was shown for the damper safety position For proper operation of a device equipped with electrical actuators it is recommended that the rated voltage housed tolerance of 24V 2 or 230V 2 Power supply devices other than listed above may cause malfunction and will not be covered by the war...

Page 14: ...1 42 45 extension number 170 fax 058 341 39 85 8 am 4 pm Mon Fri 9 WARRANTY TERMS AND CONDITIONS 1 MERCOR S A gives a 12 month quality warranty for the products and unless an agreement provides otherwise the warranty period begins on the day of purchase 2 Should physical defects be identified in the warranty period MERCOR S A undertakes to rectify them no later than 21 days from the receipt of a w...

Page 15: ... in the following cases If the buyer warranty holder makes any modifications to the original design on their own i e without consulting MERCOR S A beforehand If the periodic technical inspections and maintenance are not carried out in time or are carried out by unauthorised persons or personnel of service stations not authorised by MERCOR S A or if the product have been used improperly If any tamp...