obstruction is removed
10.
The gate will close fully, slowing down at the time previously chosen
Only perform step 11 if pedestrian access is required:
11.
Press P1/SET or P2/RADIO. The gate will begin opening. Press P1/SET at the
time where the gate is at the desired open position for pedestrian access. The gate
will close fully and the unit will exit Professional Setup.
12.
If Pedestrian Access is not required, press P1/SET and P2/RADIO
simultaneously
NOTE
The professional setup procedure will time out after four minutes if abandoned.
Testing the gate operation
Test the operation of all controls and safety devices.
Allow for the effect of weather. Wind or water may make the gates more difficult to move.
If the sensitivity is set to react to extremely light obstructions then the gates may fail to
open or close fully.
After adjustment, check that the force on an obstruction at the far end of the gate leaf
does not exceed 150N (15 kg). Use a spring balance.