5-6
Operating and Maintenance Manual
Installation
code 504275001 Rev. September 2010
5.2.9
Emergency Power Off (Remote E.P.O.)
In accordance with the standards, the UPS is fitted with an emergency device that uses a
normally closed contact (already installed on the UPS) that can be opened to activate the
emergency machine power off.
The E.P.O. terminals are:
- on the front right of the disconnector box for ARCHIMOD
®
20, 40 and 60kVA;
- on the back of the disconnector box for ARCHIMOD
®
80, 100 and 120kVA;
- in the UPS’s rear panel, terminals 3 and 4 of the 6-pole Combicon connector installed on all
contact interfaces if indicated by the silk-screen print (see 2.5.2).
If there is more than one contact interface, connect the E.P.O terminals that are on each contact
interface as follows:
• connect the E.P.O. terminals of the interfaces together in series;
• close the series created on the n.c. contact of the emergency stop.
Example of an E.P.O. connection if there are 2 contact interfaces, A and B: connect terminal 4
of interface A to terminal 3 of interface B to obtain a series. Connect terminal 3 of interface A
and terminal 4 of interface B to the n.c. contact of the emergency stop.
To connect the emergency power off device please follow these instructions:
- use a cable with double insulation;
- connect the cables as shown in the following figure;
- verify that the switch used is galvanically isolated.
Emergency Power Off Switch (NC=Normally Closed)
E.P.O.