7-7
Operating and Maintenance Manual
Control panel
code 5040275001 Rev. September 2010
7.2.3 Power Modules
PM status
PM X Info
Mod
Model of power module X
SW Vers.
Firmware version inside the power module X
HW Vers.
Hardware version of the power module X
S/N
Serial number of the power module X
Max VA
Maximum apparent power suppliable by the power module X [VA]
Max W
Maximum active power suppliable by the power module X [W]
Max Icgh
Maximum current suppliable by the battery charger of the power
module X [A]
PM
Measurements
Input X
Power
Power absorbed by the mains by the power
module X [W]
Appar. Power
Apparent power absorbed by the mains by the
power module X [VA]
Vrms.
Effective voltage in input to power module X [V
RMS]
Linked Vrms
Input line voltage to the power module X [V
RMS]
Bypass Vrms
Effective voltage in input to the power module X
for the bypass line [V RMS]
I rms
Effective current absorbed by the power module
X by the mains [A RMS]
Peak I Value
Peak current absorbed by the power module X
by the mains [A]
Frequency
Frequency of the sinusoid voltage in input to the
power module X [Hz]
Peak I Factor
Peak factor applied by the power module X to
the mains
Power factor
Power factor applied by the power module X to
the mains
Output X
Power
Active power supplied by the power module X
[W]
Appar. Power
Apparent power supplied in output by the power
module X [VA]
V rms
Effective voltage supplied in output by the power
module X [V RMS]
Linked Vrms
Line voltage in output by the power module X [V
RMS]
I rms
Effective current supplied in output by the power
module X [A RMS]
Peak I Value
Peak current supplied in output by the power
module X [A]
Frequency
Frequency of the sinusoid voltage in output from
the power module X [Hz]
Peak Factor
Peak factor of the current in output from the
power module X
Power factor
Power factor in output from the power module X
Max W
Maximum active power suppliable by the power
module X [W]
Power
Maximum active power suppliable by the power
module X, expressed as a percentage
Max VA
Maximum apparent power suppliable by the
power module X [W]
App. Power
Maximum apparent power suppliable by the
power module X, expressed as a percentage
Summary of Contents for ARCHIMOD 100
Page 2: ......
Page 69: ...12 1 Operating and Maintenance Manual Notes code 5040275001 Rev September 2010 12 Notes...
Page 70: ......
Page 71: ......