7-8
Operating and Maintenance Manual
Control panel
code 504275001 Rev. September 2010
Battery X
Voltage
Voltage measured at the ends of the batteries by
the power module X [V]
Current
Current required to the batteries from the power
module X (negative if the batteries are being
charged) [A]
Batt. Charger
Status of the battery charger inside module X
Misc. X
INV. dissip.
Temp.
Temperature of the INV dissipater
(Inverter)
of
the power module X [°C]
BST dissip.
Temp.
Temperature of the BST
(Booster)
dissipater of
the power module X [°C]
Fan speed
Fan speed expressed as a percentage of the
power module X
HV Bus pos.
Voltage on the DC BUS positive of the power
module X [V]
HV Bus neg.
Voltage on the DC BUS negative of the power
module Xm [V]
PM Historical
Data
Run Time
Total time working
Battery time
Total time running on battery
BattCharg Time Total time the battery charger has been working
Bypass int.
Total number of Bypass interventions
Battery int.
Total number of battery interventions
Dumper int.
Total number of Dumper interventions
No.Overheat
Total number of overheatings
No. Overloads
Total number of overloads
No. HV Bus run Total number of overvoltages on the Bus
No. Out DC
Level
Total number of continuous voltage presences in output from the
PMs
INDICATION
Press ENTER to change the X value and consequently vary the power module from where you
read data.
Diagnostics (*)
Reset PM
Errors
Deletes the memory of errors found in the power module.
PM SW
update (*)
Update all
the PMs
It allows the sequential and automatic updating of the internal software of all the UPS
power modules. Press ‘ENTER’ to start the procedure. If the update is unnecessary
the following message appears on the display:
‘PM SW versions updated!’ Press ‘ESC’ to exit the frame.
Update a single
PM
It allows the updating of the internal software of a single power module. Using the
‘ARROW’ keys you select the module you wish to update (‘PM00’ indicates the
module at the top on the left, going on to the last one at the bottom on the right).
By pressing ‘ENTER’ key a frame appears that gives a comparison between the
software that is actually in the module selected and the software you are about to
load. Press ‘ENTER’ to start the update procedure.
Once updated, the message ‘PM SW version updated!’ appears on the display. Press
‘ESC’ to exit the frame.
(*) Available in the ‘Service Mode’ only