7-9
Operating and Maintenance Manual
Control panel
code 5040275001 Rev. September 2010
7.2.4 Events
Events
Visual display
All
Displays all the events
Critical
Displays events that have generated critical alarms
Warning
Displays events that have generated non critical
alarms
Info
Displays events that have generated simple informa-
tion
Deletion
All
Deletes all the events
Critical
Deletes events that have generated critical alarms
Warning
Deletes events that have generated non critical alarms
Info
Deletes events that have generated simple information
7.2.5 Tools
Batteries
Battery test
Tests the batteries to check their condition and performance
Batt. Calibration
Calibrates the batteries, measuring the run down curve. If the battery is
changed, we recommend carrying out this cycle so that the UPS provides
precise information about the charge status
Battery cycle
Carries out a run down and recharge cycle so as to assess the dynamic
behaviour of the batteries
Signalling Test
Tests the luminous signals. Press ‘ENTER’ to carry out the test on the signals of the status indicator
(green, orange and red) and the acoustic signals
LCD Display Test
Tests the alphanumerical display. By pressing ‘ENTER’ all the characters available on the
alphanumerical display are shown.
7.2.6 Turning the single output phases on and off
When the inverter output is configured as three separate single-phase lines, by very lightly
pressing the On/Off key it is possible to gain access to a particular menu where you can choose
which of the three phases R,S,T to turn on or off independently from the others.
7.2.7 Shutting down the UPS ARCHIMOD
®
ATTENTION
The shutting down procedure described below is to be used only and exclusively if the load
applied to the UPS is off or does not need powering by it.
1. Check there is no need to power the connected loads.
2. Hold down the ON/OFF button on the UPS control panel.
3. Open the output switch S2.
4. Open the mains disconnecting switches (F L1, F L2 and F L3).
5. Open the battery disconnecting switches (F B+ and F B-) of the unit and of the ARCHIMOD
®
BATTERY system (if present).