8-3
Operating and Maintenance Manual
Diagnostics
code 5040275001 Rev. September 2010
FRAMES DISPLAYED WHEN SHUTTING DOWN
Message
Meaning
NO MAINS! START-UP NOT ALLOWED No mains supply. Start-up not allowed. To start the UPS on battery, select this
con
fi
guration via the display.
EMERGENCY POWER OFF!
The Emergency Power Off (EPO) is working, the EPO command has been
given by a push button or a disconnecting switch on the input line was opened
while the UPS was working.
CONFIG. INCOMPLETE FOR START-
UP!
The UPS requires a complete start-up con
fi
guration.
THREE-PHASE CIRCUIT SEQUENCE
INCORRECT!
Invalid three-phase input sequence. It needs to be checked.
THE PMs’ SW VERSIONS ARE INCOR-
RECT: UPDATE THEM!
One or more Power Modules are programmed with an invalid SW version. An
update is necessary.
Start the UPS in the Service Mode and update the Power Modules.
START-UP ERROR!
An error occurred during start-up of the UPS.
UPS SHUT DOWN BY PROGRAM-
MING!
UPS shut down by programming.
SHUTTING DOWN DUE TO AN
INCORRECT CONFIGURATION
An error occurred in con
fi
guration. UPS in shutting down.
SHUTTING DOWN DUE TO END OF
AUTONOMY
Battery charge level is too low, UPS in shutting down.
START-UP WITH BATTERY FAILED
Start-up with battery failed.
MAXIMUM TIME ON BATTERY
Battery autonomy
fi
nished. The batteries must be changed.
MAXIMUM TIME ON RESERVE
Reserve autonomy time
fi
nished. The UPS is shutting down.
LOAD NOT FED.
Load feeding interrupted.
IMPORTANT EVENTS
Message
Meaning
INVERTER FAILURE
Failure occurred in the Inverter circuit.
BOOSTER FAILURE
Failure occurred in the Booster circuit.
BATTERY CHARGER FAILURE
Failure occurred in the Battery Charger circuit.
OVERHEATING
Overheating. Check the UPS ventilation system.
OVERLOAD
Overload. Check the load level connected to the UPS.
EXCESSIVE VOLTAGE ON THE H.V.
BUS
Anomalous high voltage on the DC BUS.
EXCESSIVE DC LEVEL IN OUTPUT
The DC (Direct Current) level in output is excessive.
EXCESSIVE BATTERY VOLTAGE
Battery voltage too high.
POWER MODULE COMMUNICATION
FAILURE
Failure of the communication system with the Power Modules.
EMERGENCY
Emergency.
LOAD NOT POWERED.
Power to the loads has been interrupted.
ABNORMAL SHUTTING DOWN
UPS shut down abnormally
SHUTTING DOWN DUE TO AN OVER-
LOAD
UPS shut down due to an overload.
SHUTTING DOWN DUE TO AN EMER-
GENCY POWER OFF
UPS shut down due to an Emergency Power Off.
BATTERIES KO
Battery failure.